Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
THE BOILER MAY NOT HAVE AN EMC FILTER DEPENDING ON ITS SERIAL NO. IF IT HASN'T THEN PROCEED AS IF CONTINUITY IS OK
(IE SHORT CIRCUIT MEASURED)
Remove the live and neutral leads from the EMC filter
(IE SHORT CIRCUIT MEASURED)
Remove the live and neutral leads from the EMC filter
Measurement:
Check for continuity across;
Test 1) The live in and out.
Test 2) The neutral in and out.
Replace wires after test.
Expect short circuit on both.
Test 1) The live in and out.
Test 2) The neutral in and out.
Replace wires after test.
Expect short circuit on both.

Isolate as per TOPs P4
and refit as necessary