Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Selector switch to Heating and Hot Water
Gain access to PCB (use insulation mat as necessary)
Gain access to PCB (use insulation mat as necessary)
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Allow fan to start.
Measure voltage across the brown (1) and blue (2) leads on connector X3 on the PCB.
After approximately 5 seconds mains voltage should be present (240 VAC).
Voltage will only be present for approximately 4 seconds.
Measure voltage across the brown (1) and blue (2) leads on connector X3 on the PCB.
After approximately 5 seconds mains voltage should be present (240 VAC).
Voltage will only be present for approximately 4 seconds.

Isolate as per TOPs P4
and refit as necessary