Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
DHW Demand
Gain access to PCB (use Insulation Mat as required)
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Once the fan has started to run measure the voltage between pin 5 (black) on X401 to a suitable earth point.
Voltage should be approximately 6V DC.
Voltage should be approximately 6V DC.

Isolate as per TOPs P4
and refit as necessary