Set Appliance State:

Gas Off
On/Off Switch OFF
CH Demand
Isolate Mains Power to appliance as per TOPs P4
Attach pressure gauge to the inlet pressure test point
Gas On
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Observation:

Boiler On/Off Switch On.
Ensure no other gas appliances are in use.
Allow the ignition sequence to commence.
A drop in the standing pressure should be seen as the gas valve opens.
Note:
1. No other gas appliances must be in use during the test. The appliance will have 5 ignition attempts approximately 5 seconds apart and gas will only pass for approximately 3 seconds on each ignition attempt.
2. When pressure gauge is removed the pressure test point should be tightened and checked for gas tightness.