Set Appliance State:
Mains Power Off
CH Demand
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Reset appliance as necessary.
Expect the following sequence of events:
After approx.12 seconds fan runs, after approx. 24 seconds sparking commences and gas valve opens, burner then ignites and establishes (remains alight).
Click on your observation:
1. FAN RUNS BURNER IGNITES AND ESTABLISHES
2. FAN DOES NOT RUN
3. FAN RUNS BUT BURNER DOES NOT IGNITE
4. BURNER IGNITES BUT DOES NOT ESTABLISH
5. BURNER IGNITES BUT BAFFLES OUT OR FLAME LIFTS OFF
6. EXPLOSIVE / DELAYED IGNITION
Expect the following sequence of events:
After approx.12 seconds fan runs, after approx. 24 seconds sparking commences and gas valve opens, burner then ignites and establishes (remains alight).
Click on your observation:
1. FAN RUNS BURNER IGNITES AND ESTABLISHES
2. FAN DOES NOT RUN
3. FAN RUNS BUT BURNER DOES NOT IGNITE
4. BURNER IGNITES BUT DOES NOT ESTABLISH
5. BURNER IGNITES BUT BAFFLES OUT OR FLAME LIFTS OFF
6. EXPLOSIVE / DELAYED IGNITION