Set Appliance State:
Mains Power Off
DHW Demand
Boiler stat to MID range
Gas On
| WARNING! Mains voltage is expected during test, follow TOPs P4 live testing procedure |
Measurement:
Allow fan to run and boiler to fire and allow system to reach a reasonable operating temperature.
Turn off demand.
Using telegan temp clamps measure the temperature of the flow and return pipes close to the boiler and ascertain temperature difference between flow and return.
Expected differential approx 11 °C.
Click on your observation:
1. DIFFERENTIAL OK NOISE DUE TO EXCESSIVE HEAT
2.DIFFERENTIAL INCORRECT NOISE LOCAL BOILING
3.DIFFERENTIAL OK SYSTEM NOISE
Turn off demand.
Using telegan temp clamps measure the temperature of the flow and return pipes close to the boiler and ascertain temperature difference between flow and return.
Expected differential approx 11 °C.
Click on your observation:
1. DIFFERENTIAL OK NOISE DUE TO EXCESSIVE HEAT
2.DIFFERENTIAL INCORRECT NOISE LOCAL BOILING
3.DIFFERENTIAL OK SYSTEM NOISE