Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
DHW Demand
Pump is not an integral part of the appliance and will be found elsewhere on the system
Boiler thermostat in Off position
WARNING! Mains voltage is expected during test, follow TOPs P4 live testing procedure
Mains Power On

Observation:

Allow pump to start remove heating demand.
Does the pump stop quickly (i.e. within a second or two)?
If vent plug is removed to ascertain pump running then precautions must be taken to catch water that will escape.