XSol Diagnostic System

Interactive Test Sequence Navigator

Welcome to the XSol Diagnostic System

This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.

Start Diagnostic Sequence

or choose a specific test below:

POTTERTON KINGFISHER

GLOBALLY REPLACED

Next: &7, *

NO FAULT FOUND

Next: nff

DHW OPERATION

EXTERNAL CONTROL CALLING FOR HEAT

Next: &606, ?47, ?49, ?51, ?55, ?267

SYSTEM PRESSURE RISE

ENSURE EXTERNAL CONTROLS ARE CALLING FOR HEAT

Next: &1, !f59

CH OPERATION

EXTERNAL CONTROLS CALLING FOR HEAT

Next: &2, ?37, ?39, ?41, ?43, ?60

FAN RUNS CH DEMAND

EXTERNAL CONTROLS CALLING FOR HEAT

Next: &710, f11

POTTERTON KINGFISHER

{ISOLATEMAINSPOWER}<

Next: &5, !f8

OPERATION PUMP OVERRUN

GAIN ACCESS TO SYSTEM PUMP
ATTACH A TEMPERATURE CLAMP TO THE FLOW PIPE FROM THE APPLIANCE

Next: &nff, !f611

BURNER PRESSURE TABLE

Next: &nff, !f613

OBSERVATION PILOT AND BURNER IGNITES

EXTERNAL CONTROL CALLING FOR HEAT

Next: &3, ?711, ?713, ?717, ?796

PUMP 1

PCB CONTROL UNIT

Next: End

PUMP 2

PCB CONTROL UNIT

Next: End

FAULT OPEN

Next: End

RESISTANCE TOO LOW 1

THERMISTOR - PRECISION ENGINEERING

Next: End

LOW PRESSURE 1

GAS SUPPLY

Next: End

DOES THE PUMP RUN

LINK

Next: o234-p42, *

PUMP DHW DEMAND 1

PCB CONTROL UNIT

Next: End

LOW PRESSURE 2

GAS SUPPLY

Next: End

EFFICIENCY 2

BURNER INJECTOR

Next: End

EFFICIENCY 1

BURNER INJECTOR

Next: End

DOES THE PUMP RUN DHW DEMAND

LINK

Next: o276-p52, *

FAULT CLOSED

Next: End

OUTLET PRESSURE HIGH 1

GAS VALVE

Next: End

OPEN CIRCUIT CH DEMAND

THERMISTOR - PRECISION ENGINEERING

Next: End

RESISTANCE TOO LOW 2

THERMISTOR - PRECISION ENGINEERING

Next: End

PREMATURE SHUTDOWN 1

THERMOSTAT - OVERHEAT - THERMODISC

Next: End

RESISTANCE TOO LOW 3

THERMISTOR - PRECISION ENGINEERING

Next: End

PREMATURE SHUTDOWN 2

THERMOSTAT - OVERHEAT - THERMODISC

Next: End

RESET SWITCH

USER PCB - SPECIAL

Next: End

FAULT

HARNESS MAIN

Next: End

FAULT 2

POTENTIOMETER WIRING HARNESS ASSEMBLY

Next: End

OVERHEAT

POTENTIOMETER WIRING HARNESS ASSEMBLY

Next: End

FAULT

EXPANSION VESSEL

Next: End

PUMP OVERRUN FAULTY

PCB CONTROL UNIT

Next: End

BURNER PRESSURE TABLE

Z REDIRECT

Next: End

TTB

TTB - STAT

Next: End

OPEN CIRCUIT

THERMOSTAT - OVERHEAT - THERMODISC

Next: End

SHORT CIRCUIT

THERMISTOR - PRECISION ENGINEERING

Next: End

BLOCKED

AIR PRESSURE SWITCH TUBES

Next: End

BLOCKED 1

VENTURI

Next: End

FAULT 1

POTENTIOMETER WIRING HARNESS ASSEMBLY

Next: End

FAULT

HARNESS - LIMIT THERMOSTAT/AIR PRESSURE SWITCH

Next: End

BLOCKED 2

AIR PRESSURE SWITCH TUBES

Next: End

BLOCKED 3

VENTURI

Next: End

BLOWN

FUSE 1

Next: End

OPEN CIRCUIT NO TTB

THERMOSTAT - OVERHEAT - THERMODISC

Next: End

SHORT CIRCUIT NO TTB

THERMISTOR - PRECISION ENGINEERING

Next: End

BLOCKED NO TTB

AIR PRESSURE SWITCH TUBES

Next: End

BLOCKED 1 NO TTB

VENTURI

Next: End

FAULT 1 NO TTB

POTENTIOMETER WIRING HARNESS ASSEMBLY

Next: End

FAULT NO TTB

HARNESS - LIMIT THERMOSTAT/AIR PRESSURE SWITCH

Next: End

BLOCKED 2 NO TTB

AIR PRESSURE SWITCH TUBES

Next: End

BLOCKED 3 NO TTB

VENTURI

Next: End

BLOWN NO TTB

FUSE 1

Next: End

INLET PRESSURE 3

GAS SUPPLY

Next: End

BLOCKED

BURNER INJECTOR

Next: End

GAS VALVE PILOT 1

PCB CONTROL UNIT

Next: End

PILOT ELECTRICAL

GAS VALVE

Next: End

INLET PRESSURE 1

GAS SUPPLY

Next: End

GAP

ELECTRODE C/W LEAD ASSEMBLY

Next: End

BLOCKED 1

INJECTOR 0.38/0.36 - PILOT

Next: End

BLOCKED 1

TUBE 4MM - PILOT - SPECIAL

Next: End

GAS VALVE MAIN

PCB CONTROL UNIT

Next: End

MAIN ELECTRICAL

GAS VALVE

Next: End

OPEN OR BLOCKED

AIR PRESSURE SWITCH TUBES

Next: End

BLOCKED 2

VENTURI

Next: End

BLOCKED

FLUE

Next: End

NO SPARKING

ELECTRODE C/W LEAD ASSEMBLY

Next: End

FAULT 2

HARNESS - LIMIT THERMOSTAT/AIR PRESSURE SWITCH

Next: End

INLET PRESSURE 2

GAS SUPPLY

Next: End

ELECTRICAL SAFETY CHECKS

ELECTRICAL CHECKS

Next: End

BLOCKED 1

BURNER - PILOT

Next: End

OUTLET PRESSURE LOW 1

GAS VALVE

Next: End

INTAKE BLOCKED

FLUE

Next: End

BLOCKED

BURNER

Next: End

BLOCKED 2

INJECTOR 0.38/0.36 - PILOT

Next: End

BLOCKED 2

TUBE 4MM - PILOT - SPECIAL

Next: End

FLAME SENSE

ELECTRODE C/W LEAD ASSEMBLY

Next: End

BLOWN

FUSE - MAINS

Next: End

NO DEMAND

Next: End

BLOWN

FUSE 2

Next: End

FAULT CH DEMAND 1

PUMP

Next: End

FAULT CH DEMAND 2

PUMP

Next: End

OUTLET PRESSURE LOW 2

GAS VALVE

Next: End

EFFICIENCY 1

HEAT EXCHANGER

Next: End

FAULT DHW DEMAND 1

PUMP

Next: End

OUTLET PRESSURE LOW 3

GAS VALVE

Next: End

EFFICIENCY 2

HEAT EXCHANGER

Next: End

DHW DEMAND FAULT 1

Next: End

PREMATURE SHUTDOWN CH DEMAND

PCB CONTROL UNIT

Next: End

PREMATURE SHUTDOWN DHW DEMAND

PCB CONTROL UNIT

Next: End

ON/OFF SWITCH OR MAINS VOLTAGE TO PUMP

PCB CONTROL UNIT

Next: End

FAULT DHW DEMAND

Next: End

FAULT 5

HARNESS - LIMIT THERMOSTAT/AIR PRESSURE SWITCH

Next: End

FAULT 1

HARNESS - FACIA CONNECTION

Next: End

OVERHEAT LOCKOUT

THERMOSTAT - OVERHEAT - THERMODISC

Next: End

KETTLING CH DEMAND

HEAT EXCHANGER

Next: End

OVERHEAT

KETTLING AND/OR OVERHEAT

Next: End

OVERHEAT

PCB CONTROL UNIT

Next: End

DHW DEMAND FAULT 2

Next: End

OVERHEAT

HARNESS - FACIA CONNECTION

Next: End

FAULT 3

HARNESS - LIMIT THERMOSTAT/AIR PRESSURE SWITCH

Next: End

FAULT 4

HARNESS - LIMIT THERMOSTAT/AIR PRESSURE SWITCH

Next: End

FAILED N/O OPEN

SWITCH - PRESSURE

Next: End

FAULT 2

HARNESS - FACIA CONNECTION

Next: End

FAN 2

PCB CONTROL UNIT

Next: End

FAILED N/O OPEN 2

SWITCH - PRESSURE

Next: End

FAN

PCB CONTROL UNIT

Next: End

FAULT 3 NO TTB

HARNESS - LIMIT THERMOSTAT/AIR PRESSURE SWITCH

Next: End

FAULT 4 NO TTB

HARNESS - LIMIT THERMOSTAT/AIR PRESSURE SWITCH

Next: End

FAILED N/O OPEN NO TTB

SWITCH - PRESSURE

Next: End

FAULT 2 NO TTB

HARNESS - FACIA CONNECTION

Next: End

FAN 2 NO TTB

PCB CONTROL UNIT

Next: End

FAILED N/O OPEN 2 NO TTB

SWITCH - PRESSURE

Next: End

FAN NO TTB

PCB CONTROL UNIT

Next: End

PILOT

HARNESS MAIN

Next: End

PILOT MECHANICAL

GAS VALVE

Next: End

MAIN MECHANICAL

GAS VALVE

Next: End

MAIN

HARNESS MAIN

Next: End

FAILED N/O CLOSED

SWITCH - PRESSURE

Next: End

SPARK GENERATOR

PCB CONTROL UNIT

Next: End

GAS VALVE PILOT 2

PCB CONTROL UNIT

Next: End

FLUE WAYS

HEAT EXCHANGER

Next: End

BLOCKED 2

BURNER - PILOT

Next: End

FLAME SENSE

PCB CONTROL UNIT

Next: End

FAULT

Next: End

FAN ELECTRICAL

FAN ASSEMBLY

Next: End

Boiler only heats with CH demand

CHARACTERISTIC TEST FROM DHW OPERATION

Next: !p268

Burner shuts down prematurely

CHARACTERISTIC TEST FROM CH OPERATION

Next: p38

Boiler cool, radiators cool

CHARACTERISTIC TEST FROM CH OPERATION

Next: p40

Boiler to temperature, radiators cool

CHARACTERISTIC TEST FROM CH OPERATION

Next: p42

Boiler only heats with DHW demand

CHARACTERISTIC TEST FROM CH OPERATION

Next: !p44

Boiler shuts down prematurely

CHARACTERISTIC TEST FROM DHW OPERATION

Next: p48

Boiler cool, DHW cool

CHARACTERISTIC TEST FROM DHW OPERATION

Next: p50

Boiler to temperature, DHW cool

CHARACTERISTIC TEST FROM DHW OPERATION

Next: p52

Boiler does not react to DHW demand

CHARACTERISTIC TEST FROM DHW OPERATION

Next: !p56

BOILER GOES TO OVERHEAT LOCKOUT BEFORE 82°C FLOW TEMPERATURE REACHED

CHARACTERISTIC TEST FROM RUN BOILER TO MAXIMUM TEMPERATURE

Next: !p553

KETTLING OCCURS FLOW TEMPERATURE BELOW 85°C

CHARACTERISTIC TEST FROM RUN BOILER TO MAXIMUM TEMPERATURE

Next: !p555

BOILER CONTINUES TO FIRE, TEMPERATURE ABOVE 85°C AND RISING

CHARACTERISTIC TEST FROM RUN BOILER TO MAXIMUM TEMPERATURE

Next: p558

BOILER KETTLING AND/OR OVERHEAT LOCKOUT OCCURS

CHARACTERISTIC TEST FROM CH OPERATION

Next: p61

PILOT IGNITES AND REMAINS LIT BUT MAIN BURNER DOES NOT IGNITE

CHARACTERISTIC TEST FROM OBSERVATION PILOT AND BURNER IGNITES

Next: p712

PILOT DOES NOT IGNITE

CHARACTERISTIC TEST FROM OBSERVATION PILOT AND BURNER IGNITES

Next: p714

MAIN BURNER LIGHTS, BUT BAFFLES OR DIES AWAY

CHARACTERISTIC TEST FROM OBSERVATION PILOT AND BURNER IGNITES

Next: p718

PILOT LIGHTS BUT THEN FLAME DIES AWAY

CHARACTERISTIC TEST FROM OBSERVATION PILOT AND BURNER IGNITES

Next: p797

PUMP VOLTAGE CH DEMAND

{ISOLATEMAINSPOWER}<

Next: p63, f62

POTENTIOMETER/HARNESS ASSEMBLY

{ISOLATEMAINSPOWER}
SEPARATE THE POTENTIOMETER/HARNESS ASSEMBLY AT THE INLINE CONNECTOR

Next: !p478, !f460

PUMP VOLTAGE CH DEMAND

{ISOLATEMAINSPOWER}<

Next: !p194, !f193

PUMP VOLTAGE CH DEMAND

{ISOLATEMAINSPOWER}<

Next: !p208, !f207

GAS INLET PRESSURE

{ISOLATEMAINSPOWER}<

Next: !p218, !f217

PUMP VOLTAGE DHW DEMAND

{ISOLATEMAINSPOWER}<

Next: !p238, !f237

GAS INLET PRESSURE

{ISOLATEMAINSPOWER}<

Next: !p248, !f247

TEMPERATURE SENSOR RESISTANCE

{ISOLATEMAINSPOWER}
DISCONNECT WIRES FROM THE TEMPERATURE SENSOR

Next: !p465, !f375

POTENTIOMETER/HARNESS ASSEMBLY

{ISOLATEMAINSPOWER}
SEPARATE THE POTENTIOMETER/HARNESS ASSEMBLY AT THE INLINE CONNECTOR

Next: !p562, !f563

OBSERVATION IS SPILLAGE STAT (TTB) FITTED

{ISOLATEMAINSPOWER}

Next: p615, f679

MAINS VOLTAGE SUPPLY

USE INSULATION MAT AS REQUIRED

Next: p84, f83

OVERHEAT THERMOSTAT RESISTANCE AT PCB

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR PL1 FROM THE PCB

Next: p651, f652

OVERHEAT THERMOSTAT RESISTANCE

{ISOLATEMAINSPOWER}
DISCONNECT BOTH WIRES FROM THE OVERHEAT THERMOSTAT

Next: !p653, !f654

TEMPERATURE SENSOR RESISTANCE

{ISOLATEMAINSPOWER}
DISCONNECT WIRES FROM THE TEMPERATURE SENSOR

Next: !p657, !f658

AIR PRESSURE SWITCH TUBES

{ISOLATEMAINSPOWER}
REMOVE THE AIR PRESSURE SWITCH TUBES

Next: p661, !f662

POTENTIOMETER/HARNESS ASSEMBLY

{ISOLATEMAINSPOWER}
SEPARATE THE POTENTIOMETER/HARNESS ASSEMBLY AT THE INLINE CONNECTOR

Next: !p667, !f668

AIR PRESSURE SWITCH TUBES

{ISOLATEMAINSPOWER}
REMOVE THE AIR PRESSURE SWITCH TUBES

Next: p673, !f674

APS VOLTAGE (N/C) CH DEMAND

ENSURE EXTERNAL CONTROLS ARE CALLING FOR HEAT
USE INSULATION MAT AS REQUIRED

Next: p680, f681

OVERHEAT THERMOSTAT RESISTANCE AT PCB

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR PL1 FROM THE PCB

Next: p682, f683

OVERHEAT THERMOSTAT RESISTANCE

{ISOLATEMAINSPOWER}
DISCONNECT BOTH WIRES FROM THE OVERHEAT THERMOSTAT

Next: !p684, !f685

TEMPERATURE SENSOR RESISTANCE

{ISOLATEMAINSPOWER}
DISCONNECT WIRES FROM THE TEMPERATURE SENSOR

Next: !p688, !f689

AIR PRESSURE SWITCH TUBES

{ISOLATEMAINSPOWER}
REMOVE THE AIR PRESSURE SWITCH TUBES

Next: p692, !f693

POTENTIOMETER/HARNESS ASSEMBLY

{ISOLATEMAINSPOWER}
SEPARATE THE POTENTIOMETER/HARNESS ASSEMBLY AT THE INLINE CONNECTOR

Next: !p698, !f699

AIR PRESSURE SWITCH TUBES

{ISOLATEMAINSPOWER}
REMOVE THE AIR PRESSURE SWITCH TUBES

Next: p704, !f705

GAS VALVE PILOT RESISTANCE

{ISOLATEMAINSPOWER}
REMOVE THE CONNECTOR FROM THE GAS VALVE.

Next: !p749, !f750

GAS VALVE MAIN RESISTANCE

{ISOLATEMAINSPOWER}
DISCONNECT THE CONNECTOR FROM THE GAS VALVE

Next: !p781, !f782

AIR PRESSURE SWITCH VOLTAGE (N/O) CH DEMAND

{ISOLATEMAINSPOWER}<

Next: p784, f785

AIR PRESSURE SWITCH TUBES

{ISOLATEMAINSPOWER}
REMOVE THE AIR PRESSURE SWITCH TUBES

Next: p786, !f787

PILOT FLAME PICTURE

EXTERNAL CONTROLS CALLING FOR HEAT

Next: p820, f821

PILOT INJECTOR

{ISOLATEMAINSPOWER}

Next: p822, !f823

MAINS POWER SUPPLY FUSE

{ISOLATEMAINSPOWER}
REMOVE THE FUSE FROM THE APPLIANCE MAINS POWER SUPPLY I.E. FUSED SPUR

Next: !p86, !f85

PUMP LIMPET TEST CH DEMAND

Next: p306, !f195

PUMP LIMPET TEST CH DEMAND

Next: p206, !f205

EXTERNAL BYPASS

Next: !p210, !f209

TEMPERATURE SENSOR RESISTANCE

{ISOLATEMAINSPOWER}
DISCONNECT WIRES FROM THE TEMPERATURE SENSOR

Next: p214, !f213

BURNER PRESSURE CH DEMAND

{ISOLATEMAINSPOWER}<

Next: p216, f215

GAS RATE - CH DEMAND

Next: !p220, !f251

PUMP LIMPET TEST DHW DEMAND

Next: p240, !f239

EXTERNAL BYPASS

Next: !p242, !f241

BURNER PRESSURE DHW DEMAND

{ISOLATEMAINSPOWER}<

Next: p246, f245

GAS RATE - DHW DEMAND

Next: !p249, !f250

TEMPERATURE SENSOR RESISTANCE AT PCB CONNECTOR

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR PL1 FROM THE PCB

Next: p317, f374

EXTERNAL BYPASS

Next: p318, !f319

BURNER PRESSURE CH DEMAND

{ISOLATEMAINSPOWER}<

Next: p549, !f321

SYSTEM TEMPERATURE CH DEMAND

ENSURE EXTERNAL CONTROLS ARE CALLING FOR HEAT

Next: p386, !f233

MAINS VOLTAGE FROM EXTERNAL CONTROLS AFTER SHUTDOWN CH DEMAND

{ISOLATEMAINSPOWER}<

Next: p390, !f389

TEMPERATURE SENSOR RESISTANCE

{ISOLATEMAINSPOWER}
DISCONNECT WIRES FROM THE TEMPERATURE SENSOR

Next: p391, !f392

DOES THE BOILER GO TO LOCKOUT - CH DEMAND

EXTERNAL CONTROLS CALLING FOR HEAT

Next: !p394, !f393

MAINS VOLTAGE FROM EXTERNAL CONTROLS CH DEMAND

{ISOLATEMAINSPOWER}<

Next: p212, !f211

TEMPERATURE SENSOR RESISTANCE

{ISOLATEMAINSPOWER}
DISCONNECT WIRES FROM THE TEMPERATURE SENSOR

Next: p401, !f402

DOES THE BOILER GO TO LOCKOUT - DHW DEMAND

EXTERNAL CONTROLS CALLING FOR HEAT

Next: !p404, !f403

LOCKOUT RESET SWITCH

{ISOLATEMAINSPOWER}

Next: !p409, !f408

DOES THE PUMP RUN - CH DEMAND

EXTERNAL CONTROLS CALLING FOR HEAT

Next: p204, f203

SYSTEM TEMPERATURE DHW DEMAND

ENSURE EXTERNAL CONTROLS ARE CALLING FOR HEAT

Next: p397, !f275

MAINS VOLTAGE FROM EXTERNAL CONTROL DHW DEMAND

{ISOLATEMAINSPOWER}<

Next: p244, !f382

DOES THE PUMP RUN - DHW DEMAND

EXTERNAL CONTROLS CALLING FOR HEAT

Next: p236, f235

RUN BOILER TO MAXIMUM TEMPERATURE

{ISOLATEMAINSPOWER}<

Next: !p556, ?552, ?554, ?557

CH TEMPERATURE CONTROL RESISTANCE

{ISOLATEMAINSPOWER}<

Next: !p559, f561

DOES THE PUMP RUN - CH DEMAND

EXTERNAL CONTROLS CALLING FOR HEAT

Next: p192, f191

FLUE THERMOSTAT RESISTANCE

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR PL2 FROM THE PCB

Next: p648, !f617

FAN VOLTAGE CH DEMAND

ENSURE EXTERNAL CONTROL ARE CALLING FOR HEAT
USE INSULATION MAT AS REQUIRED

Next: p65, f614

APS VOLTAGE (N/C) CH DEMAND

ENSURE EXTERNAL CONTROLS ARE CALLING FOR HEAT
USE INSULATION MAT AS REQUIRED

Next: p649, f650

AIR PRESSURE SWITCH RESISTANCE

{ISOLATEMAINSPOWER}
REMOVE THE WIRES FROM THE AIR PRESSURE SWITCH NOTING THEIR LOCATIONS

Next: p671, f672

HARNESS - FAN AND GAS VALVE

{ISOLATEMAINSPOWER}

Next: !p95, !f458

TEMPERATURE SENSOR RESISTANCE AT PCB CONNECTOR

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR PL1 FROM THE PCB

Next: p655, f656

AIR PRESSURE SWITCH RESISTANCE

{ISOLATEMAINSPOWER}
REMOVE THE WIRES FROM THE AIR PRESSURE SWITCH NOTING THEIR LOCATIONS

Next: p659, f660

CH TEMPERATURE CONTROL RESISTANCE

{ISOLATEMAINSPOWER}<

Next: p665, f666

VENTURI

{ISOLATEMAINSPOWER}

Next: !p663, !f664

HARNESS - LIMIT THERMOSTAT AND AIR PRESSURE SWITCH

{ISOLATEMAINSPOWER}

Next: !p669, !f670

FUSE 1

{ISOLATEMAINSPOWER}
REMOVE FUSE 1 FROM THE PCB MODULE

Next: !p677, !f678

VENTURI

{ISOLATEMAINSPOWER}

Next: !p675, !f676

AIR PRESSURE SWITCH RESISTANCE

{ISOLATEMAINSPOWER}
REMOVE THE WIRES FROM THE AIR PRESSURE SWITCH NOTING THEIR LOCATIONS

Next: p702, f703

TEMPERATURE SENSOR RESISTANCE AT PCB CONNECTOR

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR PL1 FROM THE PCB

Next: p686, f687

AIR PRESSURE SWITCH RESISTANCE

{ISOLATEMAINSPOWER}
REMOVE THE WIRES FROM THE AIR PRESSURE SWITCH NOTING THEIR LOCATIONS

Next: p690, f691

CH TEMPERATURE CONTROL RESISTANCE

{ISOLATEMAINSPOWER}<

Next: p696, f697

VENTURI

{ISOLATEMAINSPOWER}

Next: !p694, !f695

HARNESS - LIMIT THERMOSTAT AND AIR PRESSURE SWITCH

{ISOLATEMAINSPOWER}

Next: !p700, !f701

FUSE 1

{ISOLATEMAINSPOWER}
REMOVE FUSE 1 FROM THE PCB MODULE

Next: !p708, !f709

VENTURI

{ISOLATEMAINSPOWER}

Next: !p706, !f707

OBSERVATION PILOT

EXTERNAL CONTROL CALLING FOR HEAT

Next: p759, f819

OBSERVATION SPARKING AT ELECTRODE

EXTERNAL CONTROL CALLING FOR HEAT

Next: p727, f783

GAS INLET PRESSURE

{ISOLATEMAINSPOWER}<

Next: p802, !f720

BURNER INJECTOR

{ISOLATEMAINSPOWER}

Next: !p818, !f722

GAS VALVE PILOT VOLTAGE

{ISOLATEMAINSPOWER}<

Next: p745, !f746

GAS VALVE PILOT RESISTANCE AT PCB

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR PL3 FROM THE PCB

Next: p747, f748

GAS INLET PRESSURE

{ISOLATEMAINSPOWER}<

Next: p751, !f752

SPARK ELECTRODE GAP

{ISOLATEMAINSPOWER}

Next: p753, !f754

PILOT INJECTOR

{ISOLATEMAINSPOWER}

Next: p755, !f756

PILOT PIPE

{ISOLATEMAINSPOWER}

Next: !p757, !f758

GAS VALVE MAIN VOLTAGE

{ISOLATEMAINSPOWER}<

Next: p777, !f778

GAS VALVE MAIN RESISTANCE AT PCB

{ISOLATEMAINSPOWER}
DISCONNECT CONNECTOR PL3 FROM THE PCB.

Next: !p779, f780

SPARK ELECTRODE ASSEMBLY CONDITION

{ISOLATEMAINSPOWER}
DISCONNECT THE SPARK ELECTRODE LEAD FROM THE PCB AND THE PILOT ASSEMBLY

Next: p792, !f793

VENTURI

{ISOLATEMAINSPOWER}

Next: p788, !f789

FLUE

Next: !p790, !f791

HARNESS - LIMIT THERMOSTAT AND AIR PRESSURE SWITCH

{ISOLATEMAINSPOWER}

Next: !p794, !f795

GAS INLET PRESSURE

{ISOLATEMAINSPOWER}<

Next: p798, !f799

PILOT BURNER

{ISOLATEMAINSPOWER}

Next: !p800, !f801

BURNER PRESSURE CH DEMAND

{ISOLATEMAINSPOWER}<

Next: p808, !f806

FLUE

Next: p813, !f812

INSPECTION BURNER

{ISOLATEMAINSPOWER}

Next: p719, !f817

SPARK ELECTRODE ASSEMBLY CONDITION

{ISOLATEMAINSPOWER}
DISCONNECT THE SPARK ELECTRODE LEAD FROM THE PCB AND THE PILOT ASSEMBLY

Next: !p826, !f827

PILOT PIPE

{ISOLATEMAINSPOWER}

Next: !p824, !f825

MAINS VOLTAGE FROM EXTERNAL CONTROLS CH DEMAND

{ISOLATEMAINSPOWER}<

Next: p88, !f87

FUSE 2

{ISOLATEMAINSPOWER}
REMOVE THE FUSE 2 FROM THE PCB MODULE

Next: p90, !f89

ON/OFF SWITCH RESISTANCE

{ISOLATEMAINSPOWER}
REMOVE CONNECTION PL5 FROM THE PCB

Next: p407, f186

System Information

  • Total Tests: 261
  • Sequence Logic: Decoded from encrypted .seq file
  • Navigation: Dynamic based on pass/fail results
  • Source: 4731307 GW SWIFTFLOW 100 SIT Control