Set Appliance State:
Gas Off
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Attach pressure gauge to the inlet pressure test point
(gas valve may differ to one shown in the image)
(gas valve may differ to one shown in the image)
Gas On
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Allow boiler to carry out ignition sequence and burner to ignite.
Does the inlet pressure remain satisfactory throughout boiler operation?
Note:
When pressure gauge is removed the pressure test
point should be tightened and checked for gas tightness.
Does the inlet pressure remain satisfactory throughout boiler operation?
Note:
When pressure gauge is removed the pressure test
point should be tightened and checked for gas tightness.

Isolate as per TOPs P4
and refit as necessary