XSol Diagnostic System

Interactive Test Sequence Navigator

Welcome to the XSol Diagnostic System

This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.

Start Diagnostic Sequence

or choose a specific test below:

NO FAULT FOUND

Next: nff

CASE REMOVAL


Next: &1545, !f2

POWER UP SELF TEST

CH TEMPERATURE CONTROL SET TO OFF POSITION
ENSURE APPLIANCE IS COOL

Next: &513, ?7, ?9, ?12, ?1547

OBSERVATION FAN RUNS

ENSURE APPLIANCE IS COOL

Next: &269, f1402

CH OPERATION

CH TEMPERATURE CONTROL SET TO MAX

Next: &1108, ?538, ?540, ?542, ?729

DHW OPERATION

HOT WATER DEMAND

Next: &nff, ?609, ?611

OBSERVATION BURNER IGNITION & ESTABLISH

ENSURE APPLIANCE IS COOL

Next: &44, ?270, ?276, ?516

FAULT CODE - SENSORS

NOT USED

Next: &nff, f386

FAULT CODE - MISCELLANEOUS

NOT USED

Next: &nff, f506

FAULT CODE - PARAMETER FAULT

NOT USED

Next: &nff, f499

FAULT CODE FAN FAULT

NOT USED

Next: &nff, !f1423

TYPE OF DIAGNOSTIC PROCEDURE

PLEASE SELECT FROM O

Next: &1116, !f514

STATUS CODE - TEMPERATURE PROTECTION

NOT USED

Next: &nff, f685

STATUS CODE - SHUTDOWN INPUT

NOT USED

Next: &nff, f657

STATUS CODE - COMMUNICATION FAULT

NOT USED

Next: &nff, f670

STATUS CODE - MISCELLANEOUS

NOT USED

Next: &nff, f675

FAULT CODE - OVERHEAT

NOT USED

Next: &nff, f869

OBSERVATION EXTERNAL FROST PROTECTION

ENSURE THERE ARE NO DEMANDS FOR HEATING OR HOT WATER

Next: &29, !f1103

OBSERVATION BOILER MODULATION

ATTACH TEMPERATURE CLAMP TO FLOW PIPE JUST ABOVE HEAT EXCHANGER

Next: &45, f1109

OBSERVATION SYSTEM PUMP RUNNING

CH TEMPERATURE CONTROL SET TO OFF POSITION
LOCATE & GAIN ACCESS TO SYSTEM PUMP

Next: &1102, f1117

BOILER NOISY

FLUE

Next: End

FROST PROTECTION

Next: End

MODULATION

KIT - SENSOR

Next: End

MODULATION 2

KIT - SENSOR

Next: End

MODULATION

CONTROLLER - USER INTERACTION

Next: End

BURNER DOES NOT IGNITE AND EST

COMBUSTION CONTROL UNIT

Next: End

BURNER DOES NOT IGNITE & EST 2

SET - ELECTRODES C/W SCREW & GASKET

Next: End

BURNER DOES NOT IGNITE & EST

BURNER MESH C/W GASKET

Next: End

BURNER DOES NOT IGNITE & EST

AIR INTAKE

Next: End

PUMP DOES NOT RUN

Next: End

BOILER SYS COOL

GAS INLET PRESSURE

Next: End

BOILER SYS COOL

KIT - SENSOR

Next: End

BOILER SYS COOL 2

KIT - SENSOR

Next: End

BOILER SYS COOL

CONTROLLER - USER INTERACTION

Next: End

FAULT CODE PARAMETER

HARNESS - CABLE 24V HE

Next: End

FAULT CODE PARAMETER

UNIT - PARAMETER (UNIT COMBUSTION CONTROL)

Next: End

BURNER IGNITION NO APS

KIT - SENSOR

Next: End

BURNER IGNITION NO APS

FAULT CODE RESET - OVERHEAT - FLUE STAT

Next: End

FAULT CODE OVERHEAT

KIT - SENSOR

Next: End

FAULT CODE OVERHEAT

SWITCH - PRESSURE C/W O-RING

Next: End

FAULT CODE OVERHEAT 12

KIT - SENSOR

Next: End

FAULT CODE OVERHEAT 8

KIT - SENSOR

Next: End

FAULT CODE OVERHEAT 4

SWITCH - PRESSURE C/W O-RING

Next: End

FAULT CODE OVERHEAT 9

KIT - SENSOR

Next: End

FAULT CODE OVERHEAT 2

FLUE

Next: End

FAULT CODE OVERHEAT 3

SWITCH - PRESSURE C/W O-RING

Next: End

FAULT CODE OVERHEAT 10

KIT - SENSOR

Next: End

FAULT CODE OVERHEAT 11

KIT - SENSOR

Next: End

AIR INTAKE

AIR INTAKE

Next: End

BURNER IGNITION 2

COMBUSTION CONTROL UNIT

Next: End

BURNER IGNITION

FLUE

Next: End

BURNER IGNITION

SET - ELECTRODES C/W SCREW & GASKET

Next: End

BURNER IGNITION 2

BURNER MESH C/W GASKET

Next: End

FAN RUNS

KIT - SENSOR

Next: End

FAN RUNS 2

KIT - SENSOR

Next: End

FAN RUNS 2

CONTROLLER - USER INTERACTION

Next: End

BOILER SYS COOL

FLUE

Next: End

FAN FAULT CODE

COMBUSTION CONTROL UNIT

Next: End

PARAMETER FAULT CODE

COMBUSTION CONTROL UNIT

Next: End

BOILER NOISY

COMBUSTION SEALS

Next: End

BOILER NOISY

HEAT ENGINE FLUEWAYS

Next: End

BOILER NOISY

BURNER MESH C/W GASKET

Next: End

BOILER SYS COOL

HEAT ENGINE FLUEWAYS

Next: End

BURNER DOES NOT IGNITE & EST

HEAT ENGINE FLUEWAYS

Next: End

BURNER IGNITION

HEAT ENGINE FLUEWAYS

Next: End

BURNER IGNITION 2

FLUE

Next: End

FAULT CODES

Z REDIRECTION

Next: End

GAS VALVE GONE NO POINT CHECKING ANYTHING ELSE

COMBUSTION CONTROL UNIT

Next: End

FUSE FURTHER INVESTIGATION NOT POSSIBLE INFORMATION

FUSE FURTHER INVESTIGATION

Next: End

INFORMATION RESETTING APPLIANCE

Z REDIRECTION

Next: End

CHIMNEY SWEEP ILLUMINATED SOLID

BUTTONS STUCK IN

Next: End

POWER UP SELF TEST

Next: End

CASE OFF

Z REDIRECTION

Next: End

HARNESS DTP - MAINS

CABLE ASSEMBLY / HARNESS - MAINS

Next: End

BURNER IGNITION

TRAP - C/W ELBOW - CONDENSATE

Next: End

BURNER IGNITION

GAS INLET PRESSURE

Next: End

BOILER NOISY

GAS INLET PRESSURE

Next: End

BOILER NOISY

TRAP - C/W ELBOW - CONDENSATE

Next: End

BOILER NOISEY

AIR INTAKE

Next: End

FAULT CODE SENSORS

COMBUSTION CONTROL UNIT

Next: End

FAULT CODE 2

KIT - SENSOR

Next: End

FAULT CODE

KIT - SENSOR

Next: End

STATUS CODE

Z REDIRECTION

Next: End

FAULT CODE MISCELLANEOUS

UNIT - PARAMETER (UNIT COMBUSTION CONTROL)

Next: End

DIAGNOSTIC PROCEDURE

Z REDIRECTION

Next: End

BURNER IGNITION

KIT - SENSOR

Next: End

BURNER IGNITION

SWITCH - PRESSURE C/W O-RING

Next: End

BURNER IGNITION

FAULT CODE RESET - OVERHEAT - FLUE STAT

Next: End

FAULT CODE MISC

FAULT/STATUS CODE MISCELLANEOUS

Next: End

STATUS CODE SHUTDWN 2

CONTROLLER - USER INTERACTION

Next: End

STAUS CODE COMMS

FAULT/STATUS CODE MISCELLANEOUS

Next: End

STATUS CODE MISC

COMBUSTION CONTROL UNIT

Next: End

BURNER IGNITION 2

SWITCH - PRESSURE C/W O-RING

Next: End

STATUS CODE TEMP

Next: End

STATUS CODE TEMP 2

PUMP

Next: End

STATUS CODE TEMP 5

KIT - SENSOR

Next: End

STATUS CODE TEMP 3

KIT - SENSOR

Next: End

STATUS CODE TEMP

KIT - SENSOR

Next: End

STATUS CODE TEMP 2

KIT - SENSOR

Next: End

STATUS CODE TEMP 2

Next: End

STATUS CODE TEMP 4

KIT - SENSOR

Next: End

STATUS CODE TEMP 6

KIT - SENSOR

Next: End

STATUS CODE TEMP 3

Next: End

PWR UP SELF TEST

COMBUSTION CONTROL UNIT

Next: End

LIMPET TEST

PUMP

Next: End

FAULT CODE OVERHEAT 2

PUMP

Next: End

FAULT CODE OVERHEAT 4

KIT - SENSOR

Next: End

FAULT CODE OVERHEAT 3

KIT - SENSOR

Next: End

FAULT CODE OVERHEAT 2

KIT - SENSOR

Next: End

FAULT CODE OVERHEAT

FLUE

Next: End

FAULT CODE OVERHEAT 2

SWITCH - PRESSURE C/W O-RING

Next: End

STATUS CODE TEMP 4

PUMP

Next: End

STATUS CODE TEMP 7

KIT - SENSOR

Next: End

STATUS CODE TEMP 11

KIT - SENSOR

Next: End

STATUS CODE TEMP 8

KIT - SENSOR

Next: End

STATUS CODE TEMP 10

KIT - SENSOR

Next: End

STATUS CODE TEMP 4

Next: End

STATUS CODE TEMP 9

KIT - SENSOR

Next: End

STATUS CODE TEMP 12

KIT - SENSOR

Next: End

FAULT CODE OVERHEAT

PUMP

Next: End

FAULT CODE OVERHEAT 7

KIT - SENSOR

Next: End

FAULT CODE OVERHEAT 6

KIT - SENSOR

Next: End

FAULT CODE OVERHEAT 5

KIT - SENSOR

Next: End

BOILER NOISY

INTERFACE - FLUE C/W SEAL

Next: End

BOILER NOISY

INTERFACE SUMP

Next: End

MODULATION

COMBUSTION CONTROL UNIT

Next: End

PUMP DOES NOT RUN

PUMP

Next: End

BURNER DOES NOT IGNITE & EST 2

COMBUSTION CONTROL UNIT

Next: End

BURNER DOES NOT IGNITE & EST

SET - ELECTRODES C/W SCREW & GASKET

Next: End

BURNER DOES NOT IGNITE & EST

INTERFACE - FLUE C/W SEAL

Next: End

BURNER DOES NOT IGNITE & EST

INTERFACE SUMP

Next: End

BURNER DOES NOT IGNITE EST 3

COMBUSTION CONTROL UNIT

Next: End

BOILER SYS COOL

COMBUSTION CONTROL UNIT

Next: End

PARAMETER FAULT

FAULT CODE RESET

Next: End

BURNER IGNITION NO APS

HARNESS - CABLE 24V HE

Next: End

BURNER DOES NOT IGNITE

COMBUSTION CONTROL UNIT

Next: End

FAULT CODE OVERHEAT

COMBUSTION CONTROL UNIT

Next: End

FAULT CODE OVERHEAT

HARNESS - CABLE 24V HE

Next: End

FAULT CODE OVERHEAT 8

COMBUSTION CONTROL UNIT

Next: End

FAULT CODE OVERHEAT NO APS

HARNESS - CABLE 24V HE

Next: End

FAULT CODE OVERHEAT 6

COMBUSTION CONTROL UNIT

Next: End

FAULT CODE OVERHEAT 2

HARNESS - CABLE 24V HE

Next: End

FAULT CODE OVERHEAT 7

COMBUSTION CONTROL UNIT

Next: End

FAULT CODE OVERHEAT 2 NO APS

HARNESS - CABLE 24V HE

Next: End

FAULT CODE OVERHEAT 4

COMBUSTION CONTROL UNIT

Next: End

BURNER IGNITION

INTERFACE - FLUE C/W SEAL

Next: End

BURNER IGNITION

INTERFACE SUMP

Next: End

BURNER IGNITION 3

COMBUSTION CONTROL UNIT

Next: End

FAN RUNS

COMBUSTION CONTROL UNIT

Next: End

BOILER SYS COOL

INTERFACE - FLUE C/W SEAL

Next: End

BOILER SYS COOL

INTERFACE SUMP

Next: End

BOILER SYS COOL 2

COMBUSTION CONTROL UNIT

Next: End

MISCELLANEOUS FAULT CODE

COMBUSTION CONTROL UNIT

Next: End

BOILER NOISY 2

COMBUSTION CONTROL UNIT

Next: End

2 RED FLASHES FAULT CODE FOR NO REASON

COMBUSTION CONTROL UNIT

Next: End

CHIMNEY ILLUMINATED SOLID

CONTROLLER - USER INTERACTION

Next: End

FAULT CODES 2

Z REDIRECTION

Next: End

PWR UP SELF TEST

CONTROLLER - USER INTERACTION

Next: End

FAULT CODE SENSOR

FAULT CODE RESET

Next: End

FAULT CODE

HARNESS - CABLE 24V HE

Next: End

FAULT CODE 2

HARNESS - CABLE 24V HE

Next: End

STATUS CODE 2

Z REDIRECTION

Next: End

FAULT CODE MISCELLANEOUS

FAULT CODE RESET

Next: End

BURNER IGNITION

HARNESS - CABLE 24V HE

Next: End

DHW OPERATION

Next: End

DHW OPERATION

Next: End

STATUS CODE SHUT DWN

FAULT CODE RESET

Next: End

STATUS CODE SHUTDWN

CONTROLLER - USER INTERACTION

Next: End

STATUS CODE SHUTDWN

BL TERMINALS - LINK

Next: End

STATUS CODE COMS

FAULT CODE RESET

Next: End

STATUS CODE COMMS

COMBUSTION CONTROL UNIT

Next: End

STATUS CODE MISC

FAULT CODE RESET

Next: End

STATUS CODE TEMP 2

COMBUSTION CONTROL UNIT

Next: End

STATUS CODE TEMP

COMBUSTION CONTROL UNIT

Next: End

STATUS CODE TEMP

STATUS CODE RESET - TEMP PROTECTION

Next: End

STATUS CODE TEMP 3

COMBUSTION CONTROL UNIT

Next: End

FAULT CODE OVERHEAT

FAULT CODE RESET - OVERHEAT - FLUE STAT

Next: End

FAULT CODE OVERHEAT 3

COMBUSTION CONTROL UNIT

Next: End

FAULT CODE OVERHEAT 2

COMBUSTION CONTROL UNIT

Next: End

STATUS CODE TEMP 4

COMBUSTION CONTROL UNIT

Next: End

STATUS CODE TEMP 2

STATUS CODE RESET - TEMP PROTECTION

Next: End

STATUS CODE TEMP 6

COMBUSTION CONTROL UNIT

Next: End

STATUS CODE TEMP 5

COMBUSTION CONTROL UNIT

Next: End

STATUS CODE TEMP

PUMP

Next: End

FAULT CODE OVERHEAT 2

FAULT CODE RESET - OVERHEAT - FLUE STAT

Next: End

FAULT CODE OVERHEAT 5

COMBUSTION CONTROL UNIT

Next: End

FAULT CODE OVERHEAT 3

PUMP

Next: End

FAULT CODE (CHIMNEY SWEEP LED FLASHING RED)

CHARACTERISTIC TEST FROM POWER UP SELF TEST

Next: p13

CHIMNEY SWEEP LED ILLUMINATED (SOLID RED OR GREEN)

CHARACTERISTIC TEST FROM POWER UP SELF TEST

Next: p1548

BURNER DOES NOT IGNITE & ESTABLISH

CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION & ESTABLISH

Next: p271

BURNER IGNITES BUT IS BAFFLING AND/OR NOISY

CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION & ESTABLISH

Next: p277

FAULT CODE 2 FLASHES RED OCCURS

CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITION & ESTABLISH

Next: p1291

BOILER AND RADIATORS DO NOT REACH TEMPERATURE

CHARACTERISTIC TEST FROM CH OPERATION

Next: p1233

BOILER UP TO TEMPERATURE, RADIATORS DO NOT HEAT SUFFICIENTLY

CHARACTERISTIC TEST FROM CH OPERATION

Next: p550

BOILER SHUTS DOWN OVERHEAT FAULT - 2 FLASHES RED OCCURS

CHARACTERISTIC TEST FROM CH OPERATION

Next: p543

DHW OPERATION UNSATISFACTORY

CHARACTERISTIC TEST FROM DHW OPERATION

Next: !p610

DHW DEMAND NOT RECOGNISED

CHARACTERISTIC TEST FROM DHW OPERATION

Next: !p612

NO CONNECTIONS - BL TERMINALS

CHARACTERISTIC TEST FROM INSPECTION BL TERMINALS - USER INTERFACE

Next: !p665

EXTERNAL CONNECTIONS - BL TERMINALS

CHARACTERISTIC TEST FROM INSPECTION BL TERMINALS - USER INTERFACE

Next: p667

CONTROL PANEL LEDS DO NOT ILLUMINATE

CHARACTERISTIC TEST FROM POWER UP SELF TEST

Next: p8

BOILER GOES TO TEMPERATURE PROTECTION - FLOW TEMPERATURE BELOW 80°C

CHARACTERISTIC TEST FROM TEMPERATURE PROTECTION - RUN BOILER TO MAXIMUM

Next: p722

BOILER FLOW TEMPERATURE EXCEEDS 85°C AND STILL FIRED

CHARACTERISTIC TEST FROM TEMPERATURE PROTECTION - RUN BOILER TO MAXIMUM

Next: p705

BOILER SHUTS DOWN TEMP PROTECTION - 1 FLASH GREEN OCCURS EVERY 3 SECONDS

CHARACTERISTIC TEST FROM CH OPERATION

Next: p762

BOILER GOES TO OVERHEAT - FLOW TEMPERATURE BELOW 80°C

CHARACTERISTIC TEST FROM TEMPERATURE - RUN BOILER TO MAXIMUM

Next: p1370

BOILER FLOW TEMPERATURE EXCEEDS 85°C AND STILL FIRED

CHARACTERISTIC TEST FROM TEMPERATURE PROTECTION - RUN BOILER TO MAXIMUM

Next: p828

BOILER GOES TO TEMPERATURE PROTECTION - FLOW TEMPERATURE BELOW 80°C

CHARACTERISTIC TEST FROM TEMPERATURE PROTECTION - RUN BOILER TO MAXIMUM

Next: p851

BOILER FLOW TEMPERATURE EXCEEDS 85°C AND STILL FIRED

CHARACTERISTIC TEST FROM TEMPERATURE PROTECTION - RUN BOILER TO MAXIMUM

Next: p853

STATUS CODE (CHIMNEY SWEEP LED FLASHING GREEN)

CHARACTERISTIC TEST FROM POWER UP SELF TEST

Next: p10

BOILER GOES TO OVERHEAT - FLOW TEMPERATURE BELOW 80°C

CHARACTERISTIC TEST FROM TEMPERATURE - RUN BOILER TO MAXIMUM

Next: p1361

BOILER FLOW TEMPERATURE EXCEEDS 85°C AND STILL FIRED

CHARACTERISTIC TEST FROM TEMPERATURE PROTECTION - RUN BOILER TO MAXIMUM

Next: p915

RESISTANCE THERMISTOR FLOW

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE FLOW THERMISTOR ELECTRICAL CONNECTOR

Next: p1110, !f1111

VOLTAGE PUMP AT PUMP

GAIN ACCESS TO PUMPS ELECTRICAL CONNECTIONS

Next: !p1118, !f1230

VOLTAGE RECTIFICATION AT PCB

{GAINPCBACS}
CH TEMPERATURE CONTROL SET TO OFF POSITION

Next: p1162, f1163

DISCONNECT SPARK ELECTRODE AT SPARK GENERATOR

DISCONNECT SPARK ELECTRODE LEAD FROM SPARK GENERATOR

Next: !p1166, !f1167

INSPECTION AIR INTAKE MANIFOLD

REMOVE THE AIR INTAKE MANIFOLD

Next: p1210, !f1229

PRESSURE GAS INLET

ATTACH PRESSURE GAUGE TO GAS PRESSURE INLET TEST POINT LOCATED UNDERNEATH THE BOILER

Next: p1409, !f1237

RESISTANCE SAFETY CIRCUIT AND HARNESS

REMOVE CONNECTOR X5 FROM THE PCB

Next: p1304, f1305

RESISTANCE STAT OVERHEAT

GAIN ACCESS TO OVERHEAT STAT & DISCONNECT LEADS TO STAT

Next: !p1306, !f1307

OBSERVATION AIR PRESSURE SWITCH FITTED

DOES THE APPLIANCE HAVE AN AIR PRESSURE SWITCH FITTED?

Next: p1318, f1325

RESISTANCE STAT OVERHEAT

GAIN ACCESS TO OVERHEAT STAT & DISCONNECT LEADS TO STAT

Next: p1321, !f1322

RESISTANCE SAFETY CIRCUIT AND HARNESS

REMOVE CONNECTOR X5 FROM THE PCB

Next: !p1326, f1327

RESISTANCE STAT OVERHEAT

GAIN ACCESS TO OVERHEAT STAT & DISCONNECT LEADS TO STAT

Next: !p1328, !f1329

OBSERVATION AIR PRESSURE SWITCH FITTED

DOES THE APPLIANCE HAVE AN AIR PRESSURE SWITCH FITTED?

Next: p1338, f1345

RESISTANCE STAT OVERHEAT

GAIN ACCESS TO OVERHEAT STAT & DISCONNECT LEADS TO STAT

Next: p1341, !f1342

RESISTANCE SAFETY CIRCUIT AND HARNESS

REMOVE CONNECTOR X5 FROM THE PCB

Next: !p1346, f1347

RESISTANCE STAT OVERHEAT

GAIN ACCESS TO OVERHEAT STAT & DISCONNECT LEADS TO STAT

Next: !p1348, !f1349

RESISTANCE THERMISTOR FLOW

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE FLOW THERMISTOR ELECTRICAL CONNECTOR

Next: p1403, !f1404

RESISTANCE THERMISTOR FLOW AND HARNESS

REMOVE CONNECTOR X5 FROM THE PCB

Next: p393, f388

RESISTANCE THERMISTOR FLOW

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE FLOW THERMISTOR ELECTRICAL CONNECTOR

Next: !p391, !f392

RESISTANCE THERMISTOR RETURN

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE RETURN THERMISTOR ELECTRICAL CONNECTOR

Next: !p398, !f399

INSPECTION PARAMETER UNIT

Next: p1273, !f1284

RESET APPLIANCE - FAULT/STATUS CODE DISPLAYED

CH TEMPERATURE CONTROL SET TO OFF

Next: !p507, f508

INSPECTION PARAMETER UNIT

Next: p509, !f510

RESISTANCE STAT OVERHEAT

GAIN ACCESS TO OVERHEAT STAT & DISCONNECT LEADS TO STAT

Next: p520, !f521

RESET APPLIANCE - STATUS CODE DISPLAYED

CH TEMPERATURE CONTROL SET TO OFF

Next: !p660, f659

INSPECTION BL TERMINALS - USER INTERFACE

GAIN ACCESS TO THE USER CONTROL INTERFACE PCB, (USE INSULATION MAT AS REQUIRED)

Next: !p663, ?664, ?666

RESET APPLIANCE - FAULT/STATUS CODE DISPLAYED

CH TEMPERATURE CONTROL SET TO OFF

Next: !p671, f672

INSPECTION WIRING HARNESS CONNECTIONS

{GAINPCBACS}

Next: !p673, !f674

RESET APPLIANCE - STATUS CODE DISPLAYED

CH TEMPERATURE CONTROL SET TO OFF

Next: !p676, !f678

OBSERVATION SYSTEM WATER

GAIN ACCESS TO SYSTEM AS REQUIRED

Next: p686, !f687

RESISTANCE THERMISTOR FLOW

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE FLOW THERMISTOR ELECTRICAL CONNECTOR

Next: p717, !f718

RESISTANCE THERMISTOR FLOW

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE FLOW THERMISTOR ELECTRICAL CONNECTOR

Next: p844, !f845

VOLTAGE PUMP AT PUMP

GAIN ACCESS TO PUMPS ELECTRICAL CONNECTIONS

Next: !p866, !f1231

OBSERVATION SYSTEM WATER

GAIN ACCESS TO SYSTEM AS REQUIRED

Next: p898, !f871

VOLTAGE PUMP AT PUMP

GAIN ACCESS TO PUMPS ELECTRICAL CONNECTIONS

Next: !p927, !f1232

STATUS CODES

Next: !p42, !f43

INSPECTION FLUE

Next: p1426, !f1002

RESISTANCE THERMISTOR RETURN

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE RETURN THERMISTOR ELECTRICAL CONNECTOR

Next: p1112, !f1113

RESISTANCE POTENTIOMETER - CH TEMPERATURE

DISCONNECT USER INTE

Next: !p1114, !f1115

VOLTAGE RECTIFICATION AT PCB - IGNITION

{GAINPCBACS}

Next: !p1164, f1209

INSPECTION FLUE

Next: p1211, !f1212

INSPECTION INTERFACE AND SUMP

Next: p1213, ?1215, ?1217

INSPECTION ELECTRODE IGNITION

REMOVE SPARK ELECTRODE ASSEMBLY FROM THE BOILER

Next: p1219, !f1220

INSPECTION HEAT EXCHANGER FLUEWAYS

REMOVE THE COMBUSTION CONTROL UNIT AND GAIN
ACCESS TO THE HEAT EXCHANGER FLUEWAYS

Next: p1221, !f1491

INSPECTION BURNER

Next: !p1227, !f1228

GAS RATE

Next: p1234, f1235

RESISTANCE THERMISTOR FLOW

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE FLOW THERMISTOR ELECTRICAL CONNECTOR

Next: p1251, !f1252

RESISTANCE THERMISTOR RETURN

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE RETURN THERMISTOR ELECTRICAL CONNECTOR

Next: p1253, !f1254

RESISTANCE POTENTIOMETER - CH TEMPERATURE

DISCONNECT USER INTE

Next: !p1255, !f1256

RESISTANCE HARNESS PARAMETER UNIT

REMOVE CONNECTOR X5 FROM THE PCB
DISCONNECT ELECTRICAL CONNECTOR TO PARAMETER UNIT

Next: p1277, !f1278

RESET APPLIANCE - FAULT/STATUS CODE DISPLAYED

CH TEMPERATURE CONTROL SET TO OFF

Next: !p1285, !f1424

OBSERVATION AIR PRESSURE SWITCH FITTED

DOES THE APPLIANCE HAVE AN AIR PRESSURE SWITCH FITTED?

Next: p517, f1303

FAULT CODES

Next: !p16, !f15

RESISTANCE SAFETY CIRCUIT AND HARNESS

REMOVE CONNECTOR X5 FROM THE PCB

Next: !p1319, f1320

RESISTANCE SWITCH AIR PRESSURE

GAIN ACCESS TO AIR PRESSURE SWITCH AND DISCONNECT LEADS

Next: !p1323, !f1324

RESISTANCE SAFETY CIRCUIT AND HARNESS

REMOVE CONNECTOR X5 FROM THE PCB

Next: !p1339, f1340

RESISTANCE SWITCH AIR PRESSURE

GAIN ACCESS TO AIR PRESSURE SWITCH AND DISCONNECT LEADS

Next: !p1343, !f1344

INSPECTION FLUE

Next: p1357, !f1358

OPERATION AIR PRESSURE SWITCH

REMOVE AIR PRESSURE SWITCH AND DISCONNECT LEADS

Next: !p1359, !f1360

OBSERVATION AIR PRESSURE SWITCH FITTED

DOES THE APPLIANCE HAVE AN AIR PRESSURE SWITCH FITTED?

Next: p913, !f1369

OBSERVATION AIR PRESSURE SWITCH FITTED

DOES THE APPLIANCE HAVE AN AIR PRESSURE SWITCH FITTED?

Next: p826, !f1378

INSPECTION AIR INTAKE MANIFOLD

REMOVE THE AIR INTAKE MANIFOLD

Next: p1380, !f1381

OBSERVATION SPARK GENERATOR

{GAINPCBACS}
REMOVE SPARK IGNITION LEAD FROM THE SPARK GENERATOR AND MAKE SAFE

Next: p1382, !f1383

INSPECTION FLUE

Next: p1384, !f1385

INSPECTION INTERFACE AND SUMP

Next: p1386, ?1388, ?1390

INSPECTION ELECTRODE IGNITION

REMOVE SPARK ELECTRODE ASSEMBLY FROM THE BOILER

Next: p1392, !f1393

INSPECTION HEAT EXCHANGER FLUEWAYS

REMOVE THE COMBUSTION CONTROL UNIT AND GAIN
ACCESS TO THE HEAT EXCHANGER FLUEWAYS

Next: p1394, !f1493

INSPECTION BURNER

Next: !p1400, !f1401

RESISTANCE THERMISTOR RETURN

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE RETURN THERMISTOR ELECTRICAL CONNECTOR

Next: p1405, !f1406

RESISTANCE POTENTIOMETER - CH TEMPERATURE

DISCONNECT USER INTE

Next: !p1407, !f1408

INSPECTION FLUE

Next: p1410, !f1411

INSPECTION INTERFACE AND SUMP

Next: p1412, ?1414, ?1416

INSPECTION HEAT EXCHANGER FLUEWAYS

REMOVE THE COMBUSTION CONTROL UNIT AND GAIN
ACCESS TO THE HEAT EXCHANGER FLUEWAYS

Next: !p1418, !f1489

INSPECTION HEAT EXCHANGER FLUEWAYS

REMOVE THE COMBUSTION CONTROL UNIT AND GAIN
ACCESS TO THE HEAT EXCHANGER FLUEWAYS

Next: p1466, !f1465

INSPECTION BURNER

Next: !p1487, !f1485

INSPECTION FLUE

Next: !p1496, !f1497

RESISTANCE GAS VALVE

REMOVE ELECTRICAL CONNECTOR FROM THE GAS VALVE

Next: p1120, !f1542

INSPECTION BUTTON STUCK IN

Next: !p1549, !f1550

VOLTAGE MAINS AT PCB

{GAINPCBACS}

Next: p19, !f20

RESISTANCE FUSE PCB

REMOVE FUSE FROM THE PCB

Next: p21, !f1544

OBSERVATION BOILER RESPONDS

Next: !p25, !f795

INSPECTION CONDENSATE

Next: p280, !f281

PRESSURE GAS INLET

ATTACH PRESSURE GAUGE TO GAS PRESSURE INLET TEST POINT LOCATED UNDERNEATH THE BOILER

Next: p340, !f341

PRESSURE GAS INLET

ATTACH PRESSURE GAUGE TO GAS PRESSURE INLET TEST POINT LOCATED UNDERNEATH THE BOILER

Next: p1498, !f283

INSPECTION CONDENSATE

Next: p342, !f343

INSPECTION AIR INTAKE MANIFOLD

REMOVE THE AIR INTAKE MANIFOLD

Next: p929, !f345

RESET APPLIANCE - FAULT CODE

CH TEMPERATURE CONTROL SET TO OFF

Next: !p389, !f390

RESISTANCE THERMISTOR RETURN AND HARNESS

REMOVE CONNECTOR X5 FROM THE PCB

Next: p387, f397

INSPECTION WIRING HARNESS CONNECTIONS

{GAINPCBACS}

Next: !p1425, !f650

RESISTANCE SAFETY CIRCUIT AND HARNESS

REMOVE CONNECTOR X5 FROM THE PCB

Next: p518, f519

RESISTANCE SWITCH AIR PRESSURE

GAIN ACCESS TO AIR PRESSURE SWITCH AND DISCONNECT LEADS

Next: !p522, !f523

OBSERVATION SYSTEM WATER

GAIN ACCESS TO SYSTEM AS REQUIRED

Next: p812, !f614

OBSERVATION SYSTEM WATER

GAIN ACCESS TO SYSTEM AS REQUIRED

Next: p807, !f552

DISCONNECT EXTERNAL BL CONNECTIONS

REMOVE EXTERNAL CONN

Next: !p668, !f669

OPERATION AIR PRESSURE SWITCH

REMOVE AIR PRESSURE SWITCH AND DISCONNECT LEADS

Next: p1495, !f683

OBSERVATION SYSTEM PUMP RUNNING

CH TEMPERATURE CONTROL SET TO OFF POSITION
LOCATE & GAIN ACCESS TO SYSTEM PUMP

Next: p688, f865

PUMP LIMPET TEST

Next: p690, !f691

RESET APPLIANCE - STATUS CODE - TEMPERATURE PROTECTION

ENSURE BOILER IS COOL

Next: p692, f716

TEMPERATURE PROTECTION - RUN BOILER TO MAXIMUM

ATTACH TEMPERATURE CLAMP TO FLOW PIPE

Next: !p721, ?702, ?704

RESISTANCE THERMISTOR FLOW

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE FLOW THERMISTOR ELECTRICAL CONNECTOR

Next: p706, !f707

RESISTANCE THERMISTOR RETURN

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE RETURN THERMISTOR ELECTRICAL CONNECTOR

Next: !p708, !f709

RESISTANCE THERMISTOR RETURN

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE RETURN THERMISTOR ELECTRICAL CONNECTOR

Next: !p719, !f720

TEMPERATURE FLOW & RETURN DIFFERENTIAL

ENSURE BOILER IS COOL
ATTACH TEMPERATURE CLAMPS TO FLOW & RETURN PIPE

Next: p723, !f724

RESISTANCE THERMISTOR FLOW

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE FLOW THERMISTOR ELECTRICAL CONNECTOR

Next: p725, !f726

RESISTANCE THERMISTOR RETURN

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE RETURN THERMISTOR ELECTRICAL CONNECTOR

Next: !p727, !f728

OBSERVATION SYSTEM WATER

GAIN ACCESS TO SYSTEM AS REQUIRED

Next: p839, !f764

VOLTAGE EXTERNAL CONTROLS

Next: p17, !f18

PUMP LIMPET TEST

Next: p808, !f809

INSPECTION SYSTEM BYPASS

Next: !p810, !f811

PUMP LIMPET TEST

Next: p813, !f814

RESET APPLIANCE - FAULT CODE - OVERHEAT

ENSURE BOILER IS COOL

Next: p815, f1310

TEMPERATURE - RUN BOILER TO MAXIMUM

ATTACH TEMPERATURE CLAMP TO FLOW PIPE JUST ABOVE HEAT EXCHANGER

Next: !p823, ?825, ?827

RESISTANCE STAT OVERHEAT

GAIN ACCESS TO OVERHEAT STAT & DISCONNECT LEADS TO STAT

Next: p833, !f834

RESISTANCE THERMISTOR FLOW

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE FLOW THERMISTOR ELECTRICAL CONNECTOR

Next: p829, !f830

RESISTANCE THERMISTOR RETURN

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE RETURN THERMISTOR ELECTRICAL CONNECTOR

Next: !p831, !f832

INSPECTION FLUE

Next: p835, !f836

OPERATION AIR PRESSURE SWITCH

REMOVE AIR PRESSURE SWITCH AND DISCONNECT LEADS

Next: !p837, !f838

PUMP LIMPET TEST

Next: p840, !f841

RESET APPLIANCE - STATUS CODE - TEMPERATURE PROTECTION

ENSURE BOILER IS COOL

Next: p842, f843

TEMPERATURE PROTECTION - RUN BOILER TO MAXIMUM

ATTACH TEMPERATURE CLAMP TO FLOW PIPE

Next: !p848, ?850, ?852

RESISTANCE THERMISTOR RETURN

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE RETURN THERMISTOR ELECTRICAL CONNECTOR

Next: !p846, !f847

TEMPERATURE FLOW & RETURN DIFFERENTIAL

ENSURE BOILER IS COOL
ATTACH TEMPERATURE CLAMPS TO FLOW & RETURN PIPE

Next: p858, !f859

RESISTANCE THERMISTOR FLOW

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE FLOW THERMISTOR ELECTRICAL CONNECTOR

Next: p854, !f855

RESISTANCE THERMISTOR RETURN

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE RETURN THERMISTOR ELECTRICAL CONNECTOR

Next: !p856, !f857

RESISTANCE THERMISTOR FLOW

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE FLOW THERMISTOR ELECTRICAL CONNECTOR

Next: p860, !f861

RESISTANCE THERMISTOR RETURN

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE RETURN THERMISTOR ELECTRICAL CONNECTOR

Next: !p862, !f863

OBSERVATION SYSTEM PUMP RUNNING

CH TEMPERATURE CONTROL SET TO OFF POSITION
LOCATE & GAIN ACCESS TO SYSTEM PUMP

Next: p899, f926

PUMP LIMPET TEST

Next: p900, !f901

RESET APPLIANCE - FAULT CODE - OVERHEAT

ENSURE BOILER IS COOL

Next: p902, f1330

TEMPERATURE - RUN BOILER TO MAXIMUM

ATTACH TEMPERATURE CLAMP TO FLOW PIPE JUST ABOVE HEAT EXCHANGER

Next: !p910, ?912, ?914

RESISTANCE STAT OVERHEAT

GAIN ACCESS TO OVERHEAT STAT & DISCONNECT LEADS TO STAT

Next: p1356, !f921

RESISTANCE THERMISTOR FLOW

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE FLOW THERMISTOR ELECTRICAL CONNECTOR

Next: p916, !f917

RESISTANCE THERMISTOR RETURN

REMOVE THE AIR INTAKE AND FLUE MANIFOLDS
REMOVE RETURN THERMISTOR ELECTRICAL CONNECTOR

Next: !p918, !f919

INSPECTION INTERFACE AND SUMP

Next: p1000, ?1019, ?1021

System Information

  • Total Tests: 368
  • Sequence Logic: Decoded from encrypted .seq file
  • Navigation: Dynamic based on pass/fail results
  • Source: 4731307 GW SWIFTFLOW 100 SIT Control