Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Remove the burner assembly from the boiler
Measurement:
Inspect the spark electrode for general condition.
Make sure the gap to the burner is 10mm (+/- 1mm) and the gap between the probes is 4mm (+/- 0.5mm).
Check for continuity (zero resistance) between the ends of the ignition electrode.
Make sure the gap to the burner is 10mm (+/- 1mm) and the gap between the probes is 4mm (+/- 0.5mm).
Check for continuity (zero resistance) between the ends of the ignition electrode.

Isolate as per TOPs P4