Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
CH temperature control to max
Attach temperature clamp to flow pipe just above heat exchanger
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Allow the boiler to ignite and run on central heating operation.
Turn the CH temperature control to the 60°C position.
If the flow temperature is already at 60°C or above the boiler should either maintain flow temperature or shut down, if flow temperature is below 60°C the boiler should continue to increase flow temperature to approximately 60°C then either maintain the flow temperature or shut down.
Note.
To reduce the time taken for this test, reduce the heating circuit by turning off some radiators.
Turn the CH temperature control to the 60°C position.
If the flow temperature is already at 60°C or above the boiler should either maintain flow temperature or shut down, if flow temperature is below 60°C the boiler should continue to increase flow temperature to approximately 60°C then either maintain the flow temperature or shut down.
Note.
To reduce the time taken for this test, reduce the heating circuit by turning off some radiators.