Set Appliance State:

Gas Off
Isolate Mains Power to appliance as per TOPs P4
DHW Demand
Remove the electrode lead from the spark generator
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Observation:

Allow the boiler to run and ignition sequence to commence.
Listen to the spark generator, can sparking be heard?
Note:
If the appliance locks out reset as necessary until the test is complete.