Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Attach temperature clamps to the flow and return pipes as indicated by the red arrows
Gas On
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Allow fan to run and boiler to fire. Measure the temperature differential as the noise occurs or if continual noise after approximately 5 minutes.
Expected differential approx. 11-20 °C
Click on your observation:
DIFFERENTIAL OK NOISE DUE TO EXCESSIVE HEAT
DIFFERENTIAL NOT OK OR NOISE IS LOCAL BOILING
DIFFERENTIAL OK SYSTEM NOISE
Expected differential approx. 11-20 °C
Click on your observation:
DIFFERENTIAL OK NOISE DUE TO EXCESSIVE HEAT
DIFFERENTIAL NOT OK OR NOISE IS LOCAL BOILING
DIFFERENTIAL OK SYSTEM NOISE