Set Appliance State:
Mains Power Off
CH Demand
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Allow boiler to fire.
Remove heating demand.
The fan should overrun for approximately 30 seconds,
The pump should overrun for approximately. 3 minutes.
Note:
The pump is not a an integral part of the appliance and is located elsewhere on the system.
Remove heating demand.
The fan should overrun for approximately 30 seconds,
The pump should overrun for approximately. 3 minutes.
Note:
The pump is not a an integral part of the appliance and is located elsewhere on the system.