Set Appliance State:
Mains Power Off
CH Demand
Place temperature clamps on flow and return pipes as shown
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Reset appliance as necessary and allow the boiler to
complete its self check.
Set the appliance to max rate by holding the       button
until Max is shown on the display.
Measure the differential between the
flow and return for at least 2 minutes.
Differential should be approximately 20°C or less.
Note:
Differential may be higher on initial start-up.
complete its self check.
Set the appliance to max rate by holding the       button
until Max is shown on the display.
Measure the differential between the
flow and return for at least 2 minutes.
Differential should be approximately 20°C or less.
Note:
Differential may be higher on initial start-up.