Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Gain access to PCB (use Insulation Mat as required)
Disconnect plug from flow thermistor (located at the top back of the heat exchanger)
Disconnect connector LV1 from the PCB
Disconnect plug from flow thermistor (located at the top back of the heat exchanger)
Disconnect connector LV1 from the PCB
Measurement:
Check for continuity (zero resistance) of each of the
wires, in turn, running between the red wires on LV1
(pins 6 and 7) to the flow thermistor.
Also inspect the harness for good overall condition.
wires, in turn, running between the red wires on LV1
(pins 6 and 7) to the flow thermistor.
Also inspect the harness for good overall condition.

Isolate as per TOPs P4
and refit as necessary