Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Attach temperature clamps to the flow and return pipework as indicated by the red arrows
Gas On
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Allow fan to run and boiler to fire.
Measure the temperature differential as the noise occurs or if continual noise after approximately 5 minutes.
Expected differential approx. 11-20 °C
Click on your observation:
DIFFERENTIAL OK NOISE DUE TO EXCESSIVE HEAT
DIFFERENTIAL NOT OK OR NOISE IS LOCAL BOILING
DIFFERENTIAL OK SYSTEM NOISE
Measure the temperature differential as the noise occurs or if continual noise after approximately 5 minutes.
Expected differential approx. 11-20 °C
Click on your observation:
DIFFERENTIAL OK NOISE DUE TO EXCESSIVE HEAT
DIFFERENTIAL NOT OK OR NOISE IS LOCAL BOILING
DIFFERENTIAL OK SYSTEM NOISE