Set Appliance State:
Mains Power Off
CH Demand
DHW Demand
On/Off Switch ON
Boiler Stat set to 1/3 Position
Boiler Stat set to 1/3 Position
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Allow the boiler to reach temperature and the burner to extinguish.
Increase the Boiler thermostat to the maximum position.
Observe the appliance it should re fire after a maximum of 5 minutes.
Note:
To reduce heat up time the boiler can be operated in either DHW or CH mode, some radiators can be turned off to reduce heat up time.
Increase the Boiler thermostat to the maximum position.
Observe the appliance it should re fire after a maximum of 5 minutes.
Note:
To reduce heat up time the boiler can be operated in either DHW or CH mode, some radiators can be turned off to reduce heat up time.