Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Set Multimeter to AC Volts Set meter to measure AC Volts
CH Demand
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Measurement:

Approximately 20 seconds after the fan starts measure the
voltage between the two red wires at CON12 on the PCB.
Voltage should stay above 160V AC but should be seen to fluctuate to approximately 230V AC as shown in the multimeter to the right.
Note:
Boiler will attempt ignition 5 times before going to lockout,
with approximately 40 seconds between attempts.
Reset as necessary until test is complete.