Set Appliance State:

Gas Off
Isolate Mains Power to appliance as per TOPs P4
CH Demand
Attach a pressure gauge to the inlet pressure test point
Gas On
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Observation:

Allow boiler to begin ignition sequence.
Does the inlet pressure remain satisfactory throughout?
Note:
1. When pressure gauge is removed the pressure test point should be tightened and checked for gas tightness.
2. Refer to TOPs for more information on acceptable inlet pressures.
3. Gas valve electrical connections may differ in appearance but test remains the same.