FUSE INVESTIGATION TREE (MAINS)
HEADER FOR MAINS FUSE INVESTIGATION - NOT USED
OBSERVATION BOILER STANDBY
NO DEMANDS
OBSERVATION RUN BOILER TO MAX TEMP
ATTACH A TEMPERATURE
OBSERVATION FAN RUNS
ENSURE BOILER IS COOL
BOILER STAT SET TO MAX (6)
OBSERVATION PUMP RUNNING
LOCATE SYSTEM PUMP
OBSERVATION BURNER IGNITES AND ESTABLISHES
REFIT CASE IF IT WAS REMOVED PREVIOUSLY
PRESSURE BURNER
ATTACH A PRESSURE GAUGE TO THE BURNER PRESSURE TEST POINT
OBSERVATION PUMP OVERRUN
CHECK IF THE PUMP IS
NO LEDS TREE FOR FAN NOT RUNNING
INTENTIONALLY BLANK - HEADER FOR NO LEDS TREE
GRAVITY DHW OPERATION UNSATISFACTORY TREE
OUTSIDE MODEL
FUSE INVESTIGATION TREE (PCB FUSE)
HEADER FOR PCB FUSE INVESTIGATION - NOT USED
NEW QADAI OPTIONS
OUTSIDE MODEL
LED 3 AND 4 ILLUMINATED
Z REDIRECT
LED 3 OFF LED 4 FLASHING
Z REDIRECT
LED 3 OFF LED 4 ILLUMINATED
Z REDIRECT
LED3 ILLMINATED LED 4 OFF
PC ADM BOARD
LED 3 FLASHING SLOW LED 4 OFF
Z REDIRECT
OPERATION CH - RUNS BUT RADS COOL
KIT - MAIN BURNER
PRESSURE BURNER
INLET PRESSURE
OPERATION CH - NOISY
SYSTEM PRESSURE / AIR IN SYSTEM
OPERATION CH - NOISY
PUMP
COMBUSTION TEST
INLET PRESSURE
COMBUSTION TEST
KIT - INSULATION
COMBUSTION TEST
BURNER FITMENT
COMBUSTION TEST
KIT - MAIN BURNER
COMBUSTION TEST
KIT - HEAT EXCHANGER (FLUEWAYS)
COMBUSTION TEST
FLUE
OBSERVATION PILOT & BURNER IGNITES - NO PILOT - STIFF
KIT - FAN ASSEMBLY
OBSERVATION PILOT & BURNER IGNITES - NO PILOT
KIT - PRESSURE SENSING TUBES
OBSERVATION PILOT & BURNER IGNITES - NO PILOT
PRESSURE SWITCH
OBSERVATION PILOT & BURNER IGNITES - NO PILOT
KIT - FAN ASSEMBLY - VENTURI
OBSERVATION PILOT & BURNER IGNITES - NO PILOT
KIT - HEAT EXCHANGER (FLUEWAYS)
OBSERVATION PILOT & BURNER IGNITES - NO PILOT
AIR PRESSURE SENSING TUBE
NO GLOW SEEN - RESISTANCE
KIT - ELECTRODE HSI
OBSERVATION FAN RUNS
KIT - RESET - SINGLE POLE HEATING SWITCH
OBSERVATION FAN RUNS - OVERHEAT INVESTIGATION
SYSTEM PRESSURE / AIR IN SYSTEM
OVERHEAT INESTIGATION
KIT - THERMOSTAT HARNESS
OBSERVATION FAN RUNS - OVERHEAT INVESTIGATION
KIT- POTENTIOMETER - HARNESS
OPERATION CH - UP TO TEMP RADS COOL
SYSTEM PRESSURE / AIR IN SYSTEM
OBSERVATION PUMP OVERRUN
PC ADM BOARD
OBSERVATION FAN RUNS - NO LEDS
KIT - MAINS HARNESS - CONTROL BOX
NO LEDS
FUSE - MAINS
NO LEDS
PCB FUSE
NO LEDS - NO VOLTAGE TO EXT CONTROLS
PC ADM BOARD
NO LEDS - EXT CONTROLS
HARNESS - EXT CONTROLS - RESET SWITCH - OVERHEAT
NO LEDS - EXT CONTROLS - 1 WIRE
HARNESS - EXT CONTROLS - RESET SWITCH - OVERHEAT
NO LEDS - OVERHEAT INVESTIGATION
SYSTEM PRESSURE / AIR IN SYSTEM
NO LEDS - OVERHEAT INESTIGATION
KIT - THERMOSTAT HARNESS
NO LEDS - OVERHEAT INVESTIGATION
KIT- POTENTIOMETER - HARNESS
NO LEDS PUMP RUNS
KIT- POTENTIOMETER - HARNESS
NO LEDS - FLOW
KIT - THERMOSTAT HARNESS
NO LEDS
KIT - PRESSURE SENSING TUBES
NO LEDS
KIT - FAN ASSEMBLY - VENTURI
NO LEDS - OPEN CIRCUIT
KIT - LIMIT THERMOSTAT
NO LEDS
KIT - RESET - SINGLE POLE HEATING SWITCH
NO LEDS - FAN
KIT - FAN HARNESS
OBSERVATION FAN RUNS - OPEN CIRCUIT
KIT - LIMIT THERMOSTAT
OBSERVATION FAN RUNS - LED3 FLASHING - FLOW
KIT - THERMOSTAT HARNESS
OBSERVATION FAN RUNS - LED3 FLASHING - RETURN
KIT - THERMOSTAT HARNESS
OPERATION CH - SHUTS DOWN TOO EARLY - RETURN
KIT - THERMOSTAT HARNESS
OPERATION CH - SHUTS DOWN TOO EARLY - FLUE
KIT - THERMOSTAT HARNESS
NO LEDS - RETURN
KIT - THERMOSTAT HARNESS
NO LEDS - FLUE
KIT - THERMOSTAT HARNESS
OBSERVATION FAN RUNS - FLUE
KIT - THERMOSTAT HARNESS
OBSERVATION FAN RUNS - RETURN
KIT - THERMOSTAT HARNESS
OBSERVATION PUMP RUNS
HARNESS - PUMP
OBSERVATION BOILER IGNITES AND ESTABLISHES
KIT - RESET - SINGLE POLE HEATING SWITCH
FUSE INVESTIGATION
KIT - THERMOSTAT HARNESS (FUSE INVESTIGATION)
OBSERVATION FAN RUNS - LED4 ON LED3 OFF
KIT - PRESSURE SENSING TUBES
OBSERVATION FAN RUNS - LED4 ON LED3 OFF
KIT - FAN ASSEMBLY - VENTURI
OBSERVATION FAN RUNS - LED3 FLASHING - FLUE
KIT - THERMOSTAT HARNESS
OVERHEAT INVESTIGATION
PUMP - NOT RUNNING
OVERHEAT INVESTIGATION - NO VOLTAGE TO PUMP
PC ADM BOARD
OVERHEAT INVESTIGATION
HARNESS - PUMP
NO LEDS - OVERHEAT INVESTIGATION
PUMP - NOT RUNNING
NO LEDS - OVERHEAT INVESTIGATION
HARNESS - PUMP
LED 3 FLASHING FAST LED 4 OFFOVERHEAT INVESTIGATION
PUMP - NOT RUNNING
LED 3 FLASHING FAST LED 4 OFF - NO VOLTAGE TO PUMP
PC ADM BOARD
LED 3 FLASHING FAST LED 4 OFFOVERHEAT INVESTIGATION
HARNESS - PUMP
LED 3 FLASHING FAST LED 4 OFF - OVERHEAT INVESTIGATION
SYSTEM PRESSURE / AIR IN SYSTEM
LED 3 FLASHING FAST LED 4 OFF OVERHEAT INESTIGATION
KIT - THERMOSTAT HARNESS
LED 3 FLASHING FAST LED 4 OFF - OVERHEAT INVESTIGATION
KIT- POTENTIOMETER - HARNESS
LED 3 FLASHING FAST LED 4 OFF - OPEN CIRCUIT
KIT - LIMIT THERMOSTAT
LED 3 FLASHING FAST LED 4 - FLOW
KIT - THERMOSTAT HARNESS
LED 3 FLASHING FAST LED 4 - RETURN
KIT - THERMOSTAT HARNESS
LED 3 FLASHING FAST LED 4 - FLUE
KIT - THERMOSTAT HARNESS
OPERATION DHW - WRONG TEMP
KIT- POTENTIOMETER - HARNESS
FUSE INVESTIGATION (MAINS) INTERNAL FUSE
KIT - FIXINGS - GENERAL
FUSE INVESTIGATION - MAINS INTERNAL FUSE
KIT - FAN ASSEMBLY
FUSE INVESTIGATION INTERNAL FUSE
KIT - ELECTRODE HSI
FUSE INVESTIGATION INTERNAL FUSE
KIT - THERMOSTAT HARNESS (FUSE INVESTIGATION)
FUSE FURTHER INVESTIGATION (PCB)
FUSE FURTHER INVESTIGATION (PCB)
BLANK FOR DIAGNOSTICS LITE 2
Z REDIRECT
BLANK FOR QUICK ACCESS DATA AND INFORMATION
Z REDIRECT
FLOW - QADAI
KIT - THERMOSTAT HARNESS
RETURN - QADAI
KIT - THERMOSTAT HARNESS
FLUE - QADAI
KIT - THERMOSTAT HARNESS
NO VOLTAGE TO FAN QADAI
PC ADM BOARD
INCORRECT RESISTANCE QADAI
KIT - FAN ASSEMBLY
INCORRECT RESISTANCE QADAI
KIT - ELECTRODE HSI
NO VOLTAGE TO HOT SURFACE IGNITOR QADAI
PC ADM BOARD
NO VOLTAGE TO GAS VALVE QADAI
PC ADM BOARD
NO VOLTAGE TO PUMP QADAI
PC ADM BOARD
INCORRECT RESISTANCE QADAI
KIT- POTENTIOMETER - HARNESS
OBSERVATION IS PUMP WIRED VIA BOILER QADAI 2
Z REDIRECT
INFORMATION CASE REMOVAL
Z REDIRECT
OPERATION CH - SHUTS DOWN TOO EARLY - FLOW
KIT - THERMOSTAT HARNESS
OPERATION CH - SHUTS DOWN TOO EARLY
KIT- POTENTIOMETER - HARNESS
OPERATION CH - RUNS BUT RADS COOL
SYSTEM PRESSURE / AIR IN SYSTEM
TYPE OF DIAGNOSTIC PROCEDURE
Z REDIRECT
FUSE INVESTIGATION - MAINS
KIT - FAN ASSEMBLY
FUSE INVESTIGATION (MAINS)
KIT - FIXINGS - GENERAL
OBSERVATION RUN BOILER TO MAX TEMP
KIT - THERMOSTAT HARNESS
OBSERVATION PUMP RUNS
FUSE - MAINS
OBSERVATION FAN RUNS
PCB FUSE
OBSERVATION PUMP RUNS - NO VOLTAGE TO EXT CONTROLS
PC ADM BOARD
OBSERVATION PUMP RUNS - EXT CONTROLS
HARNESS - EXT CONTROLS - RESET SWITCH - OVERHEAT
OBSERVATION PUMP RUNS - EXT CONTROLS - 1 WIRE
HARNESS - EXT CONTROLS - RESET SWITCH - OVERHEAT
OBSERVATION PUMP RUNS
KIT- POTENTIOMETER - HARNESS
OBSERVATION FAN RUNS - FLOW
KIT - THERMOSTAT HARNESS
OBSERVATION FAN RUNS
KIT - PRESSURE SENSING TUBES
OBSERVATION FAN RUNS
KIT - FAN ASSEMBLY - VENTURI
OBSERVATION FAN RUNS - LED ILLUMINATED - NO FAN
KIT - FAN HARNESS
OBSERVATION PUMP RUNS
PUMP - NOT RUNNING
OBSERVATION PUMP RUNS - NO VOLTAGE TO PUMP
PC ADM BOARD
FAULT CODES
Z REDIRECT
OBSERVATION PILOT & BURNER IGNITES - NO MAIN BURNER
KIT - IGNITION ELECTRODE
OBSERVATION PILOT & BURNER IGNITES - NO MAIN BURNER
INJECTOR - PILOT BURNER / KIT - INJECTOR
OBSERVATION PILOT & BURNER IGNITES - NO MAIN BURNER
PC ADM BOARD
OBSERVATION PILOT & BURNER IGNITES - NO MAIN BURNER
KIT - MAIN BURNER
OBSERVATION PILOT & BURNER IGNITES - BAFFLES
INLET PRESSURE
OBSERVATION PILOT BURNER IGNITES - BAFFLES - STIFF
KIT - FAN ASSEMBLY
OBSERVATION PILOT BURNER IGNITES - BAFFLES
KIT - INSULATION
OBSERVATION PILOT & BURNER IGNITES - BAFFLES
KIT - MAIN BURNER
OBSERVATION PILOT BURNER IGNITES - BAFFLES
KIT - HEAT EXCHANGER (FLUEWAYS)
OBSERVATION FAN RUNS - RUNS THEN STOPS - STIFF
KIT - FAN ASSEMBLY
OBSERVATION FAN RUNS - RUNS THEN STOPS
KIT - PRESSURE SENSING TUBES
OBSERVATION FAN RUNS - RUNS THEN STOPS
PRESSURE SWITCH
OBSERVATION FAN RUNS - RUNS THEN STOPS
KIT - FAN ASSEMBLY - VENTURI
OBSERVATION FAN RUNS - RUNS THEN STOPS
KIT - HEAT EXCHANGER (FLUEWAYS)
OBSERVATION FAN RUNS - RUNS THEN STOPS
AIR PRESSURE SENSING TUBE
OBSERVATION FAN RUNS - RUNS THEN STOPS
PC ADM BOARD
FUSE INVESTIGATION
KIT - ELECTRODE HSI
OPERATION CH - RUNS BUT RADS COOL
KIT - MAIN INJECTOR
PRESSURE BURNER
GAS VALVE - ADJUSTMENT
OPERATION CH - NOISY
KIT - HEAT EXCHANGER (WATERWAYS)
COMBUSTION TEST FROM DIAGNOSTIC PROCEDURE
Z REDIRECT
COMBUSTION TEST
GAS VALVE - ADJUSTMENT
COMBUSTION TEST
NO FAULT - COMBUSTION TEST
COMBUSTION TEST
KIT - GASKET GROMMET & BUSH
COMBUSTION TEST
KIT - MAIN INJECTOR
OBSERVATION PILOT & BURNER IGNITES - NO PILOT
KIT - FAN HARNESS
OBSERVATION PILOT & BURNER IGNITES - NO PILOT - SLOW
KIT - FAN ASSEMBLY
NO GLOW SEEN
KIT - ELECTRODE HSI
OBSERVATION FAN RUNS - LED3 FLASHING SLOW
PC ADM BOARD
OBSERVATION FAN RUNS - WILL NOT RESET
KIT - LIMIT THERMOSTAT
OBSERVATION FAN RUNS - OVERHEAT INVESTIGATION
NO FAULT - OVERHEAT INVESTIGATION
OBSERVATION FAN RUNS - OVERHEAT INVESTIGATION
KIT - LIMIT THERMOSTAT
OVERHEAT INVESTIGATION
PC ADM BOARD
OBSERVATION PILOT & BURNER IGNITES - NO MAIN BURNER
KIT - GAS VALVE LEAD HARNESS
OBSERVATION BURNER IGNITES AND ESTABLISHES
GAS VALVE - PILOT SOLENOID
NO APPARENT FAULT NOT WIRED TO PCB
FUSE FURTHER INVESTIGATION (MAINS)
NO LEDS
KIT - MAINS HARNESS - CONTROL BOX
NO LEDS FUSE FURTHER INVESTIGATION - MAINS
Z REDIRECT
NO LEDS - WILL NOT RESET
KIT - LIMIT THERMOSTAT
NO LEDS
NO FAULT - OVERHEAT INVESTIGATION
NO LEDS - OVERHEAT INVESTIGATION
KIT - LIMIT THERMOSTAT
NO LEDS - OVERHEAT INVESTIGATION
PC ADM BOARD
NO LEDS - BOILER RESET FAN NOW RUNS
Z REDIRECT
NO LEDS - APS
KIT - FAN HARNESS
NO LEDS
PRESSURE SWITCH
NO LEDS - OVERHEAT
HARNESS - EXT CONTROLS - RESET SWITCH - OVERHEAT
NO LEDS
PC ADM BOARD
NO LEDS
KIT - FAN ASSEMBLY
OBSERVATION FAN RUNS - LED 3 FLASHING FAST
HARNESS - EXT CONTROLS - RESET SWITCH - OVERHEAT
OBSERVATION PUMP RUNS - LEDS 3 AND 4
PC ADM BOARD
FUSE INVESTIGATION
GAS VALVE - PILOT SOLENOID
FUSE INVESTIGATION - MAINS
GAS VALVE
OBSERVATION PUMP RUNS - WIRED FROM BOILER
PUMP - NOT RUNNING
OBSERVATION FAN RUNS - LED4 ON LED3 OFF
PC ADM BOARD
OBSERVATION FAN RUNS - LED4 ON LED3 OFF
KIT - FAN HARNESS
OBSERVATION FAN RUNS - LED4 ON LED3 OFF
PRESSURE SWITCH
OBSERVATION FAN RUNS - LED3 FLASHING FAST
PC ADM BOARD
OVERHEAT INVESTIGATION - WIRED FROM BOILER
PUMP - NOT RUNNING
NO LEDS - OVERHEAT INVESTIGATION - WIRED FROM BOILER
PUMP - NOT RUNNING
LED 3 FLASHING FAST LED 4 OFF - WILL NOT RESET
KIT - LIMIT THERMOSTAT
LED 3 FLASHING FAST LED 4 OFFOVERHEAT INVESTIGATION - WIRED FROM BOILER
PUMP - NOT RUNNING
LED 3 FLASHING FAST LED 4 OFF - OVERHEAT INVESTIGATION
NO FAULT - OVERHEAT INVESTIGATION
LED 3 FLASHING FAST LED 4 OFF - OVERHEAT INVESTIGATION
KIT - LIMIT THERMOSTAT
LED 3 FLASHING FAST LED 4 OFFOBSERVATION FAN RUNS - LED 3 FLASHING FAST
HARNESS - EXT CONTROLS - RESET SWITCH - OVERHEAT
LED 3 FLASHING FAST LED 4 OFF - LED3 FLASHING FAST
PC ADM BOARD
FUSE INVESTIGATION - MAINS INTERNAL FUSE
KIT - FAN HARNESS
FUSE INVESTIGATION - MAINS - MAIN SOLENOID INTERNAL FUSE
KIT - GAS VALVE LEAD HARNESS
FUSE INVESTIGATION INTERNAL FUSE
GAS VALVE - PILOT SOLENOID
FUSE INVESTIGATION - MAINS INTERNAL FUSE
GAS VALVE
FUSE INVESTIGATION INTERNAL FUSE
PUMP WIRING
PUMP VIA BOILER
FUSE FURTHER INVESTIGATION (PCB)
BLANK FOR DIAGNOSICS LITE
Z REDIRECT
FLOW THERMISTOR SATISFACTORY
RESULT AS EXPECTED
RETURN THERMISTOR SATISFACTORY
RESULT AS EXPECTED
FLUE THERMISTOR SATISFACTORY
RESULT AS EXPECTED
FAN VOLTAGE SATISFACTORY
RESULT AS EXPECTED
FAN RESISTANCE SATISFACTORY
RESULT AS EXPECTED
HOT SURFACE IGNITOR RESISTANCE SATISFACTORY
RESULT AS EXPECTED
HOT SURFACE IGNITOR VOLTAGE SATISFACTORY
RESULT AS EXPECTED
GAS VALVE VOLTAGE SATISFACTORY
RESULT AS EXPECTED
INCORRECT RESISTANCE QADAI
GAS VALVE - PILOT SOLENOID
INCORRECT RESISTANCE QADAI
GAS VALVE
GAS VALVE RESISTANCE SATISFACTORY
RESULT AS EXPECTED
PUMP VOLTAGE SATISFACTORY
RESULT AS EXPECTED
POTENTIOMETER SATISFACTORY
RESULT AS EXPECTED
OBSERVATION IS PUMP WIRED VIA BOILER QADAI 1
Z REDIRECT
OPERATION CH - SHUTS DOWN TOO EARLY
PC ADM BOARD
FUSE INVESTIGATION - MAINS - MAIN SOLENOID
KIT - GAS VALVE LEAD HARNESS
OBSERVATION BOILER STANDBY
GAS VALVE
FUSE INVESTIGATION - MAINS
KIT - FAN HARNESS
OPERATION CH - SHUTS OFF FAN CONITNUES
GAS VALVE
OPERATION CH - SHUTS OFF FAN CONITNUES
GAS VALVE - PILOT SOLENOID
OBSERVATION RUN BOILER TO MAX TEMP
PC ADM BOARD
OBSERVATION BOILER STANDBY
PC ADM BOARD
FUSE FURTHER INVESTIGATION - MAINS
Z REDIRECT
OBSERVATION PUMP RUNS - NO LEDS
PC ADM BOARD
FUSE FURTHER INVESTIGATION - INTERNAL
Z REDIRECT
OBSERVATION FAN RUNS - ONLY I3 LED
PC ADM BOARD
OBSERVATION FAN RUNS
KIT - FAN HARNESS
OBSERVATION FAN RUNS
PRESSURE SWITCH
OBSERVATION FAN RUNS - LED ILLUMINATED - NO FAN
KIT - FAN ASSEMBLY
OBSERVATION PILOT & BURNER IGNITES - NO MAIN BURNER
GAS VALVE - ADJUSTMENT
OBSERVATION PILOT & BURNER IGNITES - NO MAIN BURNER
KIT - MAIN INJECTOR
OBSERVATION FAN RUNS - RUNS THEN STOPS
KIT - FAN HARNESS
OBSERVATION FAN RUNS - RUNS THEN STOPS - SLOW
KIT - FAN ASSEMBLY
NO APPARENT FAULT
FUSE FURTHER INVESTIGATION (MAINS)
FUSE INVESTIGATION
PUMP WIRING
BOTH LEDS FAST FLASH
PC ADM BOARD
CORK GASKET DAMAGED
CHARACTERISTIC TEST FROM INSPECTION INJECTOR AND GASKET
INJECTOR UNSATISFACTORY
CHARACTERISTIC TEST FROM INSPECTION INJECTOR AND GASKET
LED3 IS FLASHING SLOWLY, LED 4 IS OFF
CHARACTERISTIC TEST FROM OBSERVATION WHICH LEDS ARE ILLUMINATED
OVERHEAT HAS TRIPPED BUT WILL NOT RESET
CHARACTERISTIC TEST FROM OBSERVATION HAS OVERHEAT TRIPPED
OVERHEAT HAS TRIPPED BUT RESETS - INVESTIGATE CAUSE OF OVERHEAT
CHARACTERISTIC TEST FROM OBSERVATION HAS OVERHEAT TRIPPED
OVERHEAT TRIPS BEFORE 82 DEGREES
CHARACTERISTIC TEST FROM OBSERVATION RUN BOILER TO MAX TEMP (OVERHEAT)
BOILER SIGNIFICANTLY EXCEEDS 82 DEGREES AND BURNER REMAINS LIT
CHARACTERISTIC TEST FROM OBSERVATION RUN BOILER TO MAX TEMP (OVERHEAT)
PILOT SOLENOID RESISTANCE INCORRECT
CHARACTERISTIC TEST FROM RESISTANCE GAS VALVE SOLENOIDS
MAIN SOLENOID RESISTANCE INCORRECT
CHARACTERISTIC TEST FROM RESISTANCE GAS VALVE SOLENOIDS
OVERHEAT HAS TRIPPED BUT WILL NOT RESET
CHARACTERISTIC TEST FROM OBSERVATION HAS OVERHEAT TRIPPED
OVERHEAT HAS TRIPPED BUT RESETS - INVESTIGATE CAUSE OF OVERHEAT
CHARACTERISTIC TEST FROM OBSERVATION HAS OVERHEAT TRIPPED
OVERHEAT TRIPS BEFORE 82 DEGREES
CHARACTERISTIC TEST FROM OBSERVATION RUN BOILER TO MAX TEMP (OVERHEAT)
BOILER SIGNIFICANTLY EXCEEDS 82 DEGREES AND BURNER REMAINS LIT
CHARACTERISTIC TEST FROM OBSERVATION RUN BOILER TO MAX TEMP (OVERHEAT)
PILOT SOLENOID RESISTANCE IS WRONG BUT MAIN SOLENOID IS OK
CHARACTERISTIC TEST FROM RESISTANCE GAS VALVE SOLENOIDS (FUSE INVESTIGATION)
MAIN SOLENOID RESISTANCE IS WRONG
CHARACTERISTIC TEST FROM RESISTANCE GAS VALVE SOLENOIDS (FUSE INVESTIGATION)
LED 4 ILLUMINATED, LED 3 IS OFF
CHARACTERISTIC TEST FROM OBSERVATION WHICH LEDS ARE ILLUMINATED
OVERHEAT HAS TRIPPED BUT WILL NOT RESET
CHARACTERISTIC TEST FROM OBSERVATION HAS OVERHEAT TRIPPED
OVERHEAT HAS TRIPPED BUT RESETS - INVESTIGATE CAUSE OF OVERHEAT
CHARACTERISTIC TEST FROM OBSERVATION HAS OVERHEAT TRIPPED
OVERHEAT TRIPS BEFORE 82 DEGREES
CHARACTERISTIC TEST FROM OBSERVATION RUN BOILER TO MAX TEMP (OVERHEAT)
BOILER SIGNIFICANTLY EXCEEDS 82 DEGREES AND BURNER REMAINS LIT
CHARACTERISTIC TEST FROM OBSERVATION RUN BOILER TO MAX TEMP (OVERHEAT)
PILOT SOLENOID RESISTANCE IS WRONG BUT MAIN SOLENOID IS OK
CHARACTERISTIC TEST FROM RESISTANCE GAS VALVE SOLENOIDS (FUSE INVESTIGATION)
MAIN SOLENOID RESISTANCE IS WRONG
CHARACTERISTIC TEST FROM RESISTANCE GAS VALVE SOLENOIDS (FUSE INVESTIGATION)
HEADER FLOW THERMISTOR
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
HEADER RETURN THERMISTOR
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
HEADER FAN VOLTAGE
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
HEADER FAN RESISTANCE
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
HEADER HOT SURFACE IGNITOR RESISTANCE
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
HEADER HOT SURFACE IGNITOR VOLTAGE
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
HEADER GAS VALVE RESISTANCE
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
HEADER GAS VALVE VOLTAGE
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
HEADER PUMP VOLTAGE
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
HEADER POTENTIOMETER
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
HEADER DIAGNOSTICS LITE
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
HEADER QADAI
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
PILOT SOLENOID RESISTANCE IS WRONG BUT MAIN SOLENOID IS OK
CHARACTERISTIC TEST FROM RESISTANCE GAS VALVE SOLENOIDS (FUSE INVESTIGATION)
MAIN SOLENOID RESISTANCE IS WRONG
CHARACTERISTIC TEST FROM RESISTANCE GAS VALVE SOLENOIDS (FUSE INVESTIGATION)
HEADER PUMP WIRING
CHARACTERISTIC TEST FROM NEW QADAI OPTIONS
BOILER REACHES TEMPERATURE BUT RADIATORS REMAIN COOL
CHARACTERISTIC TEST FROM OPERATION CH
BOILER SHUTS DOWN BEFORE REACHING TEMPERATURE
CHARACTERISTIC TEST FROM OPERATION CH
CH OPERATES SATISFACTORILY BUT BOILER IS NOISY
CHARACTERISTIC TEST FROM OPERATION CH
BOILER CONTINUES TO FIRE BUT RADIATORS ONLY GET WARM
CHARACTERISTIC TEST FROM OPERATION CH
DHW OPERATION UNSATISFACTORY
CHARACTERISTIC TEST FROM OPERATION DHW
BOILER DOES NOT RUN WITH DHW DEMAND
CHARACTERISTIC TEST FROM OPERATION DHW
BURNER SHUTS OFF EARLY BUT FAN CONTINUES TO RUN
CHARACTERISTIC TEST FROM OPERATION CH
BOILER FIRES WITH NO DEMAND
CHARACTERISTIC TEST FROM OBSERVATION BOILER STANDBY
PILOT STUCK ON
CHARACTERISTIC TEST FROM OBSERVATION BOILER STANDBY
FAN DOES NOT RUN
CHARACTERISTIC TEST FROM OBSERVATION FAN RUNS
FAN ONLY RUNS FOR A FEW SECONDS AT A TIME (CYCLING)
CHARACTERISTIC TEST FROM OBSERVATION FAN RUNS
LED3 IS FLASHING FAST, LED 4 IS OFF
CHARACTERISTIC TEST FROM OBSERVATION WHICH LEDS ARE ILLUMINATED
LEDS 3 AND 4 ARE ILLUMINATED
CHARACTERISTIC TEST FROM OBSERVATION WHICH LEDS ARE ILLUMINATED
NO LEDS ARE ILLUMINATED
CHARACTERISTIC TEST FROM OBSERVATION WHICH LEDS ARE ILLUMINATED
BURNER LIGHTS BUT BAFFLES OUT
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITES AND ESTABLISHES
BURNER DOES NOT IGNITE
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITES AND ESTABLISHES
BURNER LIGHTS SMOOTHLY BUT GOES OUT AFTER APPROXIMATELY 10 SECONDS (DOES NOT ESTABLISH)
CHARACTERISTIC TEST FROM OBSERVATION BURNER IGNITES AND ESTABLISHES
NO BURNER PRESSURE MEASURED
CHARACTERISTIC TEST FROM PRESSURE BURNER (IGNITION)
BURNER PRESSURE PRESENT BUT LOW
CHARACTERISTIC TEST FROM PRESSURE BURNER (IGNITION)
27/01/2023 07:37:10 2212_1_50_1 28/02/2023 13:22:22
01/02/2023 10:07:40
PRESSURE GAS INLET (OPERATION)
ATTACH A PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
PRESSURE BURNER (COMBUSTION)
ATTACH A PRESSURE GAUGE TO THE BURNER PRESSURE TEST POINT
PRESSURE GAS INLET (OPERATION)
ATTACH A PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
RESISTANCE AIR PRESSURE SWITCH WITH KIT
REMOVE THE WIRES AND
RESISTANCE HOT SURFACE IGNITOR
DISCONNECT PLUG MARKED CON12 FROM THE PCB
RESISTANCE RESET SWITCH
DISCONNECT PLUG MARKED CON9 FROM THE PCB
RESISTANCE GAS VALVE SOLENOIDS
DISCONNECT LEADS FROM THE TWO GAS VALVE SOLENOIDS
RESISTANCE PUMP
REMOVE PUMP COVER / PLUG
VOLTAGE MAINS POWER IN AT TERMINAL BLOCK
{GAINPCBACS}
RESISTANCE MAINS FUSE
REMOVE THE FUSE FROM THE FUSED SPUR
FUSE FURTHER INVESTIGATION (PCB)
THE INFORMATION PROV
FUSE FURTHER INVESTIGATION
THE INFORMATION PROV
VOLTAGE EXTERNAL CONTROLS AT PCB (PERMANENT)
{GAINPCBACS}
OBSERVATION HAS OVERHEAT TRIPPED
ENSURE BOILER IS COOL
RESISTANCE THERMISTOR - FLOW
DISCONNECT CON10 FROM PCB
RESISTANCE AIR PRESSURE SWITCH (N/C)
REMOVE THE WIRES FROM THE AIR PRESSURE SWITCH (NOTING THEIR LOCATIONS)
RESISTANCE OVERHEAT THERMOSTAT
DISCONNECT LEADS FROM OVERHEAT THERMOSTAT
RESISTANCE OVERHEAT THERMOSTAT
DISCONNECT LEADS FROM OVERHEAT THERMOSTAT
RESISTANCE RESET SWITCH
DISCONNECT PLUG MARKED CON9 FROM THE PCB
RESISTANCE AIR PRESSURE SWITCH (N/C)
REMOVE THE WIRES FROM THE AIR PRESSURE SWITCH (NOTING THEIR LOCATIONS)
OBSERVATION IS PUMP WIRED VIA BOILER
{GAINPCBACS}
OBSERVATION IS PUMP WIRED VIA BOILER
{GAINPCBACS}
OBSERVATION HAS OVERHEAT TRIPPED
ENSURE BOILER IS COOL
OBSERVATION IS PUMP WIRED VIA BOILER
{GAINPCBACS}
RESISTANCE OVERHEAT THERMOSTAT
DISCONNECT LEADS FROM OVERHEAT THERMOSTAT
RESISTANCE POTENTIOMETER
DISCONNECT POTENTIOMETER PLUG FROM PCB
RESISTANCE FAN (FUSE INVESTIGATION)
DISCONNECT LEADS FROM FAN (TAKE CARE NOT TO DAMAGE SPADES)
RESISTANCE GAS VALVE SOLENOIDS (FUSE INVESTIGATION)
DISCONNECT LEADS FROM THE TWO GAS VALVE SOLENOIDS
RESISTANCE PUMP
REMOVE PUMP COVER / PLUG
RESISTANCE GAS VALVE SOLENOIDS (FUSE INVESTIGATION)
DISCONNECT LEADS FROM THE TWO GAS VALVE SOLENOIDS
RESISTANCE FAN (FUSE INVESTIGATION)
DISCONNECT LEADS FROM FAN (TAKE CARE NOT TO DAMAGE SPADES)
VOLTAGE GAS VALVE AT PCB (DROPPING OUT)
{GAINPCBACS}
RESISTANCE THERMISTOR - FLOW
DISCONNECT CON10 FROM PCB
RESISTANCE MAINS FUSE
REMOVE THE FUSE FROM THE FUSED SPUR
FUSE FURTHER INVESTIGATION
THE INFORMATION PROV
FUSE FURTHER INVESTIGATION (PCB)
THE INFORMATION PROV
VOLTAGE EXTERNAL CONTROLS AT PCB (PERMANENT)
{GAINPCBACS}
RESISTANCE AIR PRESSURE SWITCH AND HARNESS (N/C)
DISCONNECT PLUG MARKED CON11 AT THE PCB
RESISTANCE AIR PRESSURE SWITCH (N/C)
REMOVE THE WIRES FROM THE AIR PRESSURE SWITCH (NOTING THEIR LOCATIONS)
OBSERVATION IS PUMP WIRED VIA BOILER
{GAINPCBACS}
RESISTANCE AIR PRESSURE SWITCH WITH KIT
REMOVE THE WIRES AND
RESISTANCE PUMP
REMOVE PUMP COVER / PLUG
SOCKET AND SEE POLARITY CHECK
{GAINPCBACS}
INSPECTION BURNER
REMOVE BURNER ASSEMBLY
INSPECTION BURNER
REMOVE BURNER ASSEMBLY
INSPECTION HEAT EXCHANGER
REMOVE FAN & HOOD ASSEMBLY
REMOVE HEAT EXCHANGER BAFFLES
INSPECTION INJECTOR AND GASKET
REMOVE BURNER ASSEMBLY
OBSERVATION GLOW PRESENT
GAIN ACCESS TO COMBUSTION CHAMBER
RESISTANCE AIR PRESSURE SWITCH AND HARNESS WITH KIT
REMOVE THE TUBES FRO
INSPECTION FAN VENTURI
REMOVE FAN VENTURI FROM FAN
INSPECTION HEAT EXCHANGER
REMOVE FAN & HOOD ASSEMBLY
REMOVE HEAT EXCHANGER BAFFLES
INSPECTION SENSING TUBE
REMOVE FAN FROM HOOD ASSEMBLY
OBSERVATION HAS OVERHEAT TRIPPED
ENSURE BOILER IS COOL
RESISTANCE OVERHEAT THERMOSTAT AND HARNESS
DISCONNECT PLUG MARKED CON9 FROM THE PCB
OBSERVATION PUMP RUNNING
LOCATE SYSTEM PUMP
RESISTANCE THERMISTOR - FLOW
DISCONNECT CON10 FROM PCB
RESISTANCE POTENTIOMETER
DISCONNECT POTENTIOMETER PLUG FROM PCB
OBSERVATION RUN BOILER TO MAX TEMP (OVERHEAT)
ATTACH A TEMPERATURE
RESISTANCE THERMISTOR - FLOW
DISCONNECT CON10 FROM PCB
OBSERVATION IS PUMP WIRED VIA BOILER
{GAINPCBACS}
RESISTANCE PCB FUSE
REMOVE PCB FUSE FROM HOLDER
VOLTAGE EXTERNAL CONTROLS AT PCB (DEMAND)
{GAINPCBACS}
VOLTAGE FAN AT PCB
{GAINPCBACS}
RESISTANCE HARNESS EXTERNAL CONTROLS (1 WIRE)
DISCONNECT PLUG MARKED CON6 AT THE PCB
RESISTANCE HARNESS EXTERNAL CONTROLS
DISCONNECT PLUG MARKED CON6 AT THE PCB
VOLTAGE FAN AT FAN
REMOVE COMBUSTION CASE
OBSERVATION DISCONNECT POTENTIOMETER
DISCONNECT POTENTIOMETER AT THE PCB
OBSERVATION PUMP RUNNING
LOCATE SYSTEM PUMP
RESISTANCE THERMISTOR - FLOW
DISCONNECT CON10 FROM PCB
RESISTANCE POTENTIOMETER
DISCONNECT POTENTIOMETER PLUG FROM PCB
OBSERVATION RUN BOILER TO MAX TEMP (OVERHEAT)
ATTACH A TEMPERATURE
RESISTANCE AIR PRESSURE SWITCH AND HARNESS (N/C)
DISCONNECT PLUG MARKED CON11 AT THE PCB
RESISTANCE OVERHEAT THERMOSTAT AND HARNESS
DISCONNECT PLUG MARKED CON9 FROM THE PCB
INSPECTION FAN VENTURI
REMOVE FAN VENTURI FROM FAN
RESISTANCE RESET SWITCH
DISCONNECT PLUG MARKED CON9 FROM THE PCB
RESISTANCE THERMISTOR - RETURN
DISCONNECT CON10 FROM PCB
RESISTANCE THERMISTOR - FLUE 125K @ 21 TO 550 @ 200 DEG
DISCONNECT CON10 FROM PCB
RESISTANCE THERMISTOR - RETURN
DISCONNECT CON10 FROM PCB
RESISTANCE THERMISTOR - FLUE 125K @ 21 TO 550 @ 200 DEG
DISCONNECT CON10 FROM PCB
RESISTANCE THERMISTOR - RETURN
DISCONNECT CON10 FROM PCB
RESISTANCE THERMISTOR - FLUE 125K @ 21 TO 550 @ 200 DEG
DISCONNECT CON10 FROM PCB
RESISTANCE THERMISTOR - RETURN
DISCONNECT CON10 FROM PCB
RESISTANCE THERMISTOR - FLUE 125K @ 21 TO 550 @ 200 DEG
DISCONNECT CON10 FROM PCB
RESISTANCE HARNESS PUMP
DISCONNECT PLUG MARKED CON11 AT THE PCB
SOCKET AND SEE POLARITY CHECK
{GAINPCBACS}
RESISTANCE AIR PRESSURE SWITCH AND HARNESS (N/C)
DISCONNECT PLUG MARKED CON11 AT THE PCB
INSPECTION FAN VENTURI
REMOVE FAN VENTURI FROM FAN
RESISTANCE HARNESS PUMP
DISCONNECT PLUG MARKED CON11 AT THE PCB
RESISTANCE HARNESS PUMP
DISCONNECT PLUG MARKED CON11 AT THE PCB
RESISTANCE OVERHEAT THERMOSTAT AND HARNESS
DISCONNECT PLUG MARKED CON9 FROM THE PCB
OBSERVATION PUMP RUNNING
LOCATE SYSTEM PUMP
RESISTANCE HARNESS PUMP
DISCONNECT PLUG MARKED CON11 AT THE PCB
RESISTANCE THERMISTOR - FLOW
DISCONNECT CON10 FROM PCB
RESISTANCE POTENTIOMETER
DISCONNECT POTENTIOMETER PLUG FROM PCB
OBSERVATION RUN BOILER TO MAX TEMP (OVERHEAT)
ATTACH A TEMPERATURE
RESISTANCE THERMISTOR - FLOW
DISCONNECT CON10 FROM PCB
RESISTANCE THERMISTOR - RETURN
DISCONNECT CON10 FROM PCB
RESISTANCE THERMISTOR - FLUE 125K @ 21 TO 550 @ 200 DEG
DISCONNECT CON10 FROM PCB
RESISTANCE FAN AND HARNESS (FUSE INVESTIGATION)
DISCONNECT PLUG MARKED CON11 AT THE PCB
RESISTANCE HOT SURFACE IGNITOR (FUSE INVESTIGATION)
DISCONNECT PLUG MARKED CON12 FROM THE PCB
RESISTANCE GAS VALVE AND HARNESS (FUSE INVESTIGATION)
DISCONNECT PLUG MARKED CON14 AT THE PCB
OBSERVATION IS PUMP WIRED VIA BOILER
{GAINPCBACS}
RESISTANCE PUMP AND HARNESS
DISCONNECT PLUG MARKED CON3 AT THE PCB
RESISTANCE THERMISTOR - FLOW
DISCONNECT CON10 FROM PCB
RESISTANCE THERMISTOR - RETURN
DISCONNECT CON10 FROM PCB
RESISTANCE THERMISTOR - FLUE 125K @ 21 TO 550 @ 200 DEG
DISCONNECT CON10 FROM PCB
VOLTAGE FAN AT PCB
{GAINPCBACS}
RESISTANCE FAN (FUSE INVESTIGATION)
DISCONNECT LEADS FROM FAN (TAKE CARE NOT TO DAMAGE SPADES)
RESISTANCE HOT SURFACE IGNITOR (FUSE INVESTIGATION)
DISCONNECT PLUG MARKED CON12 FROM THE PCB
VOLTAGE GAS VALVE AT PCB
{GAINPCBACS}
RESISTANCE POTENTIOMETER
DISCONNECT POTENTIOMETER PLUG FROM PCB
DIAGNOSTICS LITE
DIAGNOSIS RELIES ON
QUICK ACCESS DATA AND INFORMATION
THE TABLE BELOW SHOW
RESISTANCE GAS VALVE SOLENOIDS (FUSE INVESTIGATION)
DISCONNECT LEADS FROM THE TWO GAS VALVE SOLENOIDS
OBSERVATION IS PUMP WIRED VIA BOILER QADAI
{GAINPCBACS}
RESISTANCE THERMISTOR - FLOW
DISCONNECT CON10 FROM PCB
RESISTANCE POTENTIOMETER
DISCONNECT POTENTIOMETER PLUG FROM PCB
RESISTANCE GAS VALVE AND HARNESS (FUSE INVESTIGATION)
DISCONNECT PLUG MARKED CON14 AT THE PCB
RESISTANCE FAN AND HARNESS (FUSE INVESTIGATION)
DISCONNECT PLUG MARKED CON11 AT THE PCB
VOLTAGE EXTERNAL CONTROLS AT PCB (NO DEMAND)
{GAINPCBACS}
ENSURE NO DEMANDS
OBSERVATION WHICH LEDS ARE ILLUMINATED
{GAINPCBACS}
VOLTAGE FAN AT PCB
{GAINPCBACS}
VOLTAGE EXTERNAL CONTROLS AT PCB (DEMAND)
{GAINPCBACS}
VOLTAGE MAINS POWER IN AT TERMINAL BLOCK
{GAINPCBACS}
RESISTANCE PCB FUSE
REMOVE PCB FUSE FROM HOLDER
OBSERVATION DISCONNECT POTENTIOMETER
DISCONNECT POTENTIOMETER AT THE PCB
RESISTANCE HARNESS EXTERNAL CONTROLS (1 WIRE)
DISCONNECT PLUG MARKED CON6 AT THE PCB
RESISTANCE HARNESS EXTERNAL CONTROLS
DISCONNECT PLUG MARKED CON6 AT THE PCB
RESISTANCE THERMISTOR - FLOW
DISCONNECT CON10 FROM PCB
VOLTAGE FAN AT FAN
REMOVE COMBUSTION CASE
INSPECTION FAN VENTURI
REMOVE FAN VENTURI FROM FAN
PRESSURE GAS INLET
ATTACH A PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
PRESSURE BURNER (IGNITION)
ATTACH A PRESSURE GAUGE TO THE BURNER PRESSURE TEST POINT
INSPECTION ELECTRODE AND LEAD
DISCONNECT FLAME SEN
INSPECTION PILOT ASSEMBLY
REMOVE BURNER
REMOVE MAIN & PILOT INJECTOR ASSEMBLY
REMOVE PILOT INJECTOR
INSPECTION BURNER
REMOVE BURNER ASSEMBLY
PRESSURE GAS INLET
ATTACH A PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
PRESSURE GAS INLET
ATTACH A PRESSURE GAUGE TO THE INLET PRESSURE TEST POINT
VOLTAGE GAS VALVE AT PCB
{GAINPCBACS}
RESISTANCE GAS VALVE AND HARNESS
DISCONNECT PLUG MARKED CON14 AT THE PCB
INSPECTION BURNER
REMOVE BURNER ASSEMBLY
INSPECTION HEAT EXCHANGER
REMOVE FAN & HOOD ASSEMBLY
REMOVE HEAT EXCHANGER BAFFLES
RESISTANCE AIR PRESSURE SWITCH AND HARNESS WITH KIT
REMOVE THE TUBES FRO
INSPECTION FAN VENTURI
REMOVE FAN VENTURI FROM FAN
INSPECTION HEAT EXCHANGER
REMOVE FAN & HOOD ASSEMBLY
REMOVE HEAT EXCHANGER BAFFLES
INSPECTION SENSING TUBE
REMOVE FAN FROM HOOD ASSEMBLY
OBSERVATION FAN RUNS CONTINUALLY WITH APS MADE
REMOVE THE TUBES FRO
RESISTANCE HOT SURFACE IGNITOR (FUSE INVESTIGATION)
DISCONNECT PLUG MARKED CON12 FROM THE PCB
RESISTANCE PUMP AND HARNESS
DISCONNECT PLUG MARKED CON3 AT THE PCB