Set Appliance State:
Isolate Mains Power to appliance as per TOPs P4
Remove flame detection electrode from its housing
Remove flame detection electrode from its housing
Measurement:
Thoroughly check the electrode lead and earth lead for signs of damage, cracked ceramic, damaged insulation and cleanliness.
Measure the resistance of the electrode lead and earth lead.
Expect continuity / zero resistance.
Note:
A faulty earth connection to the flame detection electrode can cause a misdiagnosis and blame the PCB.
N.B. This fault is not picked-up in the
manufacturer's instructions.
Measure the resistance of the electrode lead and earth lead.
Expect continuity / zero resistance.
Note:
A faulty earth connection to the flame detection electrode can cause a misdiagnosis and blame the PCB.
N.B. This fault is not picked-up in the
manufacturer's instructions.

Isolate as per TOPs P4
and refit as necessary