Set Appliance State:

Set Multimeter to DC Volts Set meter to measure DC Volts
Isolate Mains Power to appliance as per TOPs P4
Gain access to PCB connections as necessary
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Measurement:

Measure voltage across connection 4 ( +ve probe to yellow lead) and connection 1 (-ve probe to black lead) on connector J11 on the control PCB.
Voltage will vary according to the boiler system pressure but
should conform approximately to the table below:
System PressureVoltage DC
0 bar0.5
0.4 bar0.8
0.8 bar1
1.2 bar1.2
1.6 bar1.6
2 bar1.8