Set Appliance State:
Gas Off
On/Off Switch OFF
Isolate Mains Power to appliance as per TOPs P4
Attach pressure gauge to inlet pressure test point
Attach pressure gauge to inlet pressure test point
Gas On
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Appliance On/Off switch On.
Reset lockout as necessary.
Allow fan to run and ignition sequence to commence.
Does the gauge show a constant inlet pressure of at least 18 mb throughout the sequence?
Note:
When pressure gauge removed test point should be tightened and checked for soundness.
Reset lockout as necessary.
Allow fan to run and ignition sequence to commence.
Does the gauge show a constant inlet pressure of at least 18 mb throughout the sequence?
Note:
When pressure gauge removed test point should be tightened and checked for soundness.
Isolate as per TOPs P4
and refit as necessary