Set Appliance State:
On/Off Switch OFF
Isolate Mains Power to appliance as per TOPs P4
Ensure DHW demand is satisfied
Close the isolation valve on the integral bypass
Ensure DHW demand is satisfied
Close the isolation valve on the integral bypass
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Appliance On/Off switch On.
Reset lockout as necessary.
Allow boiler to fire.
Does the circulation to the system improve?
After test open isolation valve on the bypass.
Reset lockout as necessary.
Allow boiler to fire.
Does the circulation to the system improve?
After test open isolation valve on the bypass.