Set Appliance State:
Mains Power Off
Isolate Mains Power to appliance as per TOPs P4
Ensure that the Appliance is switched OFF.
Room Thermostat calling for heat (if fitted).
Ensure that the Appliance is switched OFF.
Room Thermostat calling for heat (if fitted).
Measurement:
Measure a short circuit resistance across the Room Thermostat Connections 9 and 10 (on the 12 way Terminal Block).
Note:
If no Room Thermostat is installed, a factory fitted link, will be in place between connections 9 and 10.
If a Room Thermostat is fitted the link MUST be removed.
Note:
If no Room Thermostat is installed, a factory fitted link, will be in place between connections 9 and 10.
If a Room Thermostat is fitted the link MUST be removed.

Isolate as per TOPs P4
and refit as necessary