Set Appliance State:

Mains Power Off
CH Demand
Boiler Thermal Store must be at MAXIMUM TEMPERATURE, to ensure this, run the boiler until the Green Neon extinguishes, then;
Models with Programmer:
Rocker Switch to Timed, Programmer C/H demand to ON
Models without Programmer: Central Heating Switch to ON.
Note:
If the Appliance is only utilised for Hot Water (no CH System) select the "Pump runs satisfactorily." option below.
WARNING! Mains voltage is expected during test, follow TOPs P4 live testing procedure
Mains Power On

Observation:

Does the Water Pump Run?
Note:
Do not take noise or vibration as an indication that the Pump is running.