Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Measurement:
Test 1:
Measure the resistance between the pump live (top terminal) and neutral at the incoming terminal strip.
Expected resistance approximately 120 Ohms or greater.
(ErP pumps will usually be a MOhm reading)
Test 2:
Measure the resistance between the pump live (top terminal) and the earth at the incoming terminal strip.
Expected resistance greater than 1 MOhm.
(O.L is acceptable because it is greater than 1MOhm)
Are the resistances as expected?
Measure the resistance between the pump live (top terminal) and neutral at the incoming terminal strip.
Expected resistance approximately 120 Ohms or greater.
(ErP pumps will usually be a MOhm reading)
Test 2:
Measure the resistance between the pump live (top terminal) and the earth at the incoming terminal strip.
Expected resistance greater than 1 MOhm.
(O.L is acceptable because it is greater than 1MOhm)
Are the resistances as expected?