Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Attach pressure gauge to fan pressure test point
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Reset appliance if required (press and hold reset button for 5 seconds then release).
Fan pressure will read negative and should be approximately -2.5 mbar or greater.
(e.g. -3.0 mbar)
Notes:
1. The pressure measured will be negative.
2. When pressure gauge is removed, pressure test cap must be replaced.
Fan pressure will read negative and should be approximately -2.5 mbar or greater.
(e.g. -3.0 mbar)
Notes:
1. The pressure measured will be negative.
2. When pressure gauge is removed, pressure test cap must be replaced.
Isolate as per TOPs P4
and refit as necessary