Set Appliance State:
Gas Off
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Attach pressure gauge to inlet pressure test point on gas valve
Gas On
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
Reset appliance if necessary (press and hold reset button for 5 seconds, then release).
Allow the boiler to commence ignition sequence.
Does the pressure gauge show a constant inlet gas pressure above 16.5mbar? (28mbar for LPG appliances)
(Minimum mbar requirement at gas valve inlet 16.5mbar at MAX output, 28mbar for LPG appliances)
Note:
When pressure gauge is removed the test point should be tightened & checked for gas soundness.
Allow the boiler to commence ignition sequence.
Does the pressure gauge show a constant inlet gas pressure above 16.5mbar? (28mbar for LPG appliances)
(Minimum mbar requirement at gas valve inlet 16.5mbar at MAX output, 28mbar for LPG appliances)
Note:
When pressure gauge is removed the test point should be tightened & checked for gas soundness.
Isolate as per TOPs P4
and refit as necessary