Set Appliance State:
Mains Power Off
CH Demand
CH temperature control set to MAX
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Allow the boiler to run until system starts to warm, then remove CH demand.
Does the pump continue to run for approximately 3 minutes?
Does the pump continue to run for approximately 3 minutes?
Isolate as per TOPs P4
and refit as necessary