Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
CH Demand
Attach both +ve and -ve connections on FGA to their respective connections at the test points on the top of the boiler
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Observation:

With the fan running is there a differential of at least 0.5mb?
Note:
0.5mb is absolute minimum for APS to operate, if fault is intermittent and the pressure is only slightly above 0.5mb you may wish to select "differential unsatisfactory" to investigate possible issues.