Set Appliance State:
Gas Off
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Disconnect leads from spark generator and position on the edge of the housing as shown in the picture
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Reset boiler if it is in lockout.
Shortly after the fan runs can sparking be seen between the spark generator and the disconnected leads?
Shortly after the fan runs can sparking be seen between the spark generator and the disconnected leads?
Isolate as per TOPs P4
and refit as necessary