Set Appliance State:
Gas Off
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Attach pressure gauge to the inlet pressure test point
Mains reset switch On
Mains reset switch On
Gas On
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Allow fan to run and ignition sequence to commence.
Does the inlet pressure stay constant and remain above a minimum of 15 mb?
Note:
1. The manufacturer states the boiler range is able to deliver its full output at
inlet pressures as low as 15mb, however please refer to British Gas Technical Operational Procedures for further guidance regarding gas inlet working pressures.
2. When pressure gauge is removed the pressure test point should be tightened and checked for gas tightness.
Does the inlet pressure stay constant and remain above a minimum of 15 mb?
Note:
1. The manufacturer states the boiler range is able to deliver its full output at
inlet pressures as low as 15mb, however please refer to British Gas Technical Operational Procedures for further guidance regarding gas inlet working pressures.
2. When pressure gauge is removed the pressure test point should be tightened and checked for gas tightness.
Isolate as per TOPs P4
and refit as necessary