Set Appliance State:

Set Boiler Control Thermostat to MAX position
Set Multimeter to AC Volts Set meter to measure AC Volts
CH Demand
Isolate Mains Power to appliance as per TOPs P4
Gain access to PCB
Use insulation mat where necessary
Remove the black lead from the air pressure switch and make safe
External controls calling for heat
WARNING! Mains voltage is expected during test, follow TOPs P4 live testing procedure
Mains Power On

Measurement:

Allow fan to run.
Measure the voltage across the exposed terminal (NO) on the air pressure switch and the neutral (marked N) on the main connector block.
Expected voltage 230 volts AC.