Set Appliance State:
Set Boiler Control Thermostat to MAX position
CH Demand
Isolate Mains Power to appliance as per TOPs P4
External controls calling for heat
Gain access to PCB
Use insulation mat as necessary
External controls calling for heat
Gain access to PCB
Use insulation mat as necessary
| WARNING! Mains voltage is expected during test, follow TOPs P4 live testing procedure |
Measurement:
Measure the voltage across the 1st terminal marked K2 (live) and the neutral (marked N) on the main connector block in the control box.
Expected voltage 230 AC (mains voltage).
Expected voltage 230 AC (mains voltage).

Isolate as per TOPs P4
and refit as necessary