Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Set Boiler Control Thermostat to MAX position
Attach pressure gauge to burner pressure test point
Attach pressure gauge to burner pressure test point
Gas On
| WARNING! Mains voltage is expected during test, follow TOPs P4 live testing procedure |
Measurement:
Set the soft light pressure to approximately 4.5mb.
Refer to Adapt for guidance on how to set the soft light pressure.
Has it been possible to adjust the soft light pressure ?
Note:
When pressure gauge is removed pressure test point should be tightened & checked for gas soundness.
Refer to Adapt for guidance on how to set the soft light pressure.
Has it been possible to adjust the soft light pressure ?
Note:
When pressure gauge is removed pressure test point should be tightened & checked for gas soundness.
Isolate as per TOPs P4
and refit as necessary