Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
CH Demand
Set Boiler Control Thermostat to MAX position
Attach pressure gauge to burner pressure test point
Gas On
WARNING! Mains voltage is expected during test, follow TOPs P4 live testing procedure
Mains Power On

Measurement:

Reset boiler as necessary.
Allow ignition sequence to commence.
The pressure gauge should show a soft light pressure of approx. 4.5mb, then rise to its set burner pressure between 9.8mb and 12.5mb.
Does the soft light and burner pressures behave as above ?
Note:
When pressure gauge is removed pressure test point should be tightened & checked for gas soundness.