Welcome to the XSol Diagnostic System
This system provides interactive diagnostic tests with proper sequence navigation based on the decoded .seq file logic.
GLOW-WORM MICRON 30FF (FROM SNO 0035001)
WARNING - IMPORTA
OPERATIONAL SEQUENCE
NO LONGER USED
DHW OPERATION
{BLRSTATMAX}
TYPE OF DIAGNOSTIC PROCEDURE
PLEASE SELECT FROM O
ENHANCED FAULT CODES
SELECT APPROPRIATE F
EPROM / PCB / SOFTWARE ERROR
OUTSIDE MODEL
BLOCKING ERROR
OUTSIDE MODEL
FURTHER INVESTIGATION PCB
OUTSIDE MODEL
FURTHER INVESTIGATION FUSE
NOT INSIDE MODEL
FAN RUNS WITH DEMAND
{BLRSTATMAX}
EXTERNAL CONTROLS CALLING FOR HEAT
ENSURE BOILER IS COOL
OBSERVATION DOES BOILER FIRE WITH NO DEMAND
ENSURE NO DEMANDS
BURNER IGNITION
{BLRSTATMAX}
OVERHEAT OR EARTH FAULT
OUTSIDE MODEL
RADIATORS PROVIDE INSUFFICIENT HEAT
GAS INLET PRESSURE
RADIATORS PROVIDE INSUFFICIENT HEAT
THERMISTOR
BOILER COOL RADIATORS COOL
BURNER INJECTOR
BOILER NOISY PUMP RUNS HIGH
PUMP EXTERNAL
DHW TOO HOT
THERMISTOR
OPERATIONAL SEQUENCE
SYSTEM CHECKS
ENHANCED FAULT CODES
SYSTEM CHECKS
PCB ERROR CODE
PCB
LED1&2 SLOW FLASH
SOCKET AND SEE
TYPE OF DIAG PROC
SYSTEM CHECKS
ELECTRICAL CHECKS
SYSTEM CHECKS
FURTHER INV PCB
GAS VALVE + PCB
POLARITY FAULT
EARTH LEAD
FURTHER INV FUSE
GAS VALVE + FUSE
FURTHER INV RESISTANCES
THERMISTOR + FUSE
SHORTING
IGNITION ELECTRODE
BLOCKING ERROR
IGNITION LEAD ASSEMBLY
PASSING
GAS VALVE
FAN RUNS NO DEMAND
FUSE 2A
FAN RUNS WITH DEMAND
THERMISTOR
SPARKING PRESENT
AIR PRESSURE SWITCH TUBES
SPARKING PRESENT
VENTURI
NO FAN
EARTH LEAD
FAN RUNS NO DEMAND
HARNESS FAN
BOILER TO TEMPERATURE RADIATORS COOL PUMP RUNS HIGH
PUMP EXTERNAL
BURNER IGNITES BUT FLAME BAFFLES OUT OR DIES AWAY
GAS INLET PRESSURE
BURNER IGNITES BUT FLAME BAFFLES OUT OR DIES AWAY
HEAT EXCHANGER FLUE WAYS
BURNER IGNITES BUT DOES NOT ESTABLISH
IGNITION ELECTRODE AND GAP
BURNER IGNITES BUT DOES NOT ESTABLISH
HEAT EXCHANGER FLUE WAYS
BURNER IGNITES BUT DOES NOT ESTABLISH
IGNITION LEAD ASSEMBLY
NO SPARKING
AIR PRESSURE SWITCH
NO SPARKING
IGNITION ELECTRODE AND GAP
NO SPARKING
IGNITION LEAD ASSEMBLY
BURNER DOES NOT IGNITE
AIR PRESSURE SWITCH TUBES
BURNER DOES NOT IGNITE
VENTURI
BURNER IGNITION
GAS INLET PRESSURE
BOILER DOES NOT IGNITE
THERMOSTAT OVERHEAT
BURNER DOES NOT IGNITE
GAS VALVE + PCB
BURNER DOES NOT IGNITE
GAS VALVE SOLENOIDS
BURNER IGNITION
BURNER INJECTOR
EARTH FAULT
SOCKET AND SEE
OVERHEAT THERMOSTAT
THERMOSTAT OVERHEAT WATER INGRESS
LED 1 ILLU
THERMOSTAT OVERHEAT
FURTHER INV OVERHEAT LIMPET FAILED
PUMP EXTERNAL
NOT SHUTTING OFF FURTHER INV OVERHEAT
THERMISTOR
OVERHEAT FAULT
THERMISTOR
OVERHEAT INV
THERMOSTAT OVERHEAT
RADIATORS PROVIDE INSUFFICIENT HEAT
GAS VALVE
LED 1&2 SLOW FLASH
SYSTEM CHECKS
PCB ERROR CODE
SYSTEM CHECKS
BLOCKING ERROR
SYSTEM CHECKS
BOILER NOISY
HEAT EXCHANGER ASSEMBLY
FURTHER INV PCB
WATER INGRESS + PCB
FURTHER INV PCB
THERMISTOR + PCB
FURTHER INV PCB
HARNESS GAS VALVE + PCB
FAN RUNS DEMAND
FAN
FURTHER INV FUSE
THERMISTOR + FUSE
FURTHER INV FUSE
WATER INGRESS + FUSE
FURTHER INV FUSE
HARNESS GAS VALVE + FUSE
BLOCKING ERROR
PCB
FURTHER INVESTIGATION FUSE
SYSTEM CHECKS
SPARKING PRESENT
AIR PRESSURE SWITCH
PCB FURTHER INVESTIGATION
SYSTEM CHECKS
FURTHER INV PCB
PCB
CH OP BOILER TO TEMP RADS COOL
PUMP EXTERNAL
NO SPARKING
PCB
RUNNING SLOW
FAN
BURNER DOES NOT IGNITE
HARNESS OVERHEAT
BURNER DOES NOT IGNITE
HARNESS GAS VALVE + PCB
BURNER DOES NOT IGNITE
GAS VALVE
BURNER DOES NOT IGNITE
HARNESS GAS VALVE
BURNER IGNITION
BURNER
LED 1 ILLU
PCB
OVERHEAT OR EARTH FAULT
HARNESS OVERHEAT
FURTHER INV OVERHEAT NOT RUNNING
PUMP EXTERNAL
OVERHEAT LOCKOUT
OVERHEAT
OVERHEAT INV
PCB
NO FAN - MAINS SUPPLY 2
Z REDIRECT
FUSE FURTHER INVESTIGATION - MAINS
Z REDIRECT
NO FAULT
FUSE FURTHER INVESTIGATION
Boiler to temperature, radiators cool
CHARACTERISTIC TEST FROM CH OPERATION
RADIATORS HEAT BUT BOILER NOISY
CHARACTERISTIC TEST FROM CH OPERATION
Boiler cool, radiators cool
CHARACTERISTIC TEST FROM CH OPERATION
DHW too cool
CHARACTERISTIC TEST FROM DHW OPERATION
DHW too hot
CHARACTERISTIC TEST FROM DHW OPERATION
Boiler does not react to DHW demand
CHARACTERISTIC TEST FROM DHW OPERATION
RESISTANCE TO EARTH LOW OR SHORT CIRCUIT
CHARACTERISTIC TEST FROM RESISTANCE THERMISTOR TO EARTH
WATER INGRESS IN THERMISTOR POCKET
CHARACTERISTIC TEST FROM RESISTANCE THERMISTOR TO EARTH
RESISTANCE TO EARTH LOW OR SHORT CIRCUIT
CHARACTERISTIC TEST FROM RESISTANCE THERMISTOR TO EARTH
WATER INGRESS IN THERMISTOR POCKET
CHARACTERISTIC TEST FROM RESISTANCE THERMISTOR TO EARTH
Burner does not ignite
CHARACTERISTIC TEST FROM BURNER IGNITION
BURNER IGNITES BUT DOES NOT ESTABLISH
CHARACTERISTIC TEST FROM BURNER IGNITION
BURNER IGNITES BUT BAFFLES OUT
CHARACTERISTIC TEST FROM BURNER IGNITION
BOILER GOES TO LOCKOUT BEFORE REACHING TEMPERATURE
CHARACTERISTIC TEST FROM OBSERVATION RUN BOILER TO TEMP
BOILER CONTINUES FIRING PAST 85 DEGREES C
CHARACTERISTIC TEST FROM OBSERVATION RUN BOILER TO TEMP
07/10/2019 09:44:17 1908_1_50_1 22/10/2019 13:03:42
07/10/2019 13:27:46
GAS INLET PRESSURE
ATTACH PRESSURE GAUGE TO INLET PRESSURE TEST POINT
EXTERNAL CONTROLS CALLING
SOCKET AND SEE TEST
GAIN ACCESS TO APPLIANCE TERMINAL STRIP
RESISTANCE THERMISTOR TO EARTH
DISCONNECT THE THERMISTOR CONNECTOR FROM THE PCB (BLACK LEADS)
RESISTANCE GAS VALVE
REMOVE THE CONNECTOR PLUG FROM THE GAS VALVE
THERMISTOR
DISCONNECT THE THERMISTOR CONNECTOR FROM THE PCB (BLACK LEADS)
RESISTANCE GAS VALVE
REMOVE THE CONNECTOR PLUG FROM THE GAS VALVE
RESISTANCE ELECTRODE TO EARTH
DISCONNECT THE SPARK ELECTRODE FROM THE IGNITION LEAD ASSEMBLY CONNECTOR
FUSE FURTHER INVESTIGATION
THE INFORMATION PROV
VOLTAGE TO PUMP
REMOVE PUMP COVER
FAN VOLTAGE
{BLRSTATMAX}
FAN VOLTAGE
{BLRSTATMAX}
PRESSURE APS SWITCHING
DISCONNECT LEADS FROM THE AIR PRESSURE SWITCH NOTING THE CONNECTIONS
IGNITION ELECTRODE AND GAP
DISCONNECT IGNITION LEAD TO THE ELECTRODE
GAS INLET PRESSURE
ATTACH PRESSURE GAUGE TO INLET PRESSURE TEST POINT
EXTERNAL CONTROLS CALLING
RESISTANCE OVERHEAT THERMOSTAT AND HARNESS
REMOVE THE OVERHEAT CONNECTOR FROM THE PCB
THIS IS THE CONNECTOR WHICH HAS THE 2 BROWN WIRES
OVERHEAT THERMOSTAT
REMOVE ONE OF THE BROWN LEADS FROM THE OVERHEAT THERMOSTAT
ENSURE APPLIANCE IS COOL
RESISTANCE GAS VALVE
REMOVE THE CONNECTOR PLUG FROM THE GAS VALVE
RESISTANCE GAS VALVE
REMOVE THE CONNECTOR PLUG FROM THE GAS VALVE
OBSERVATION BOILER RESET OVERHEAT
ENSURE BOILER IS COOL
SOCKET AND SEE TEST
GAIN ACCESS TO APPLIANCE TERMINAL STRIP
OVERHEAT THERMOSTAT
REMOVE ONE OF THE BROWN LEADS FROM THE OVERHEAT THERMOSTAT
ENSURE APPLIANCE IS COOL
VOLTAGE TO PUMP
REMOVE PUMP COVER
INFORMATION NO VOLTAGE TO APPLIANCE
THIS APPLIANCE DOES
MAINS IN OBSERVATION REMOVE PERMANENT MAINS SUPPLY TO APPLIANCE (NO FAN)
REMOVE THE LIVE, NEU
BURNER PRESSURE
{BLRSTATMAX}
ATTACH PRESSURE GAUGE TO BURNER PRESSURE TEST POINT
THERMISTOR
DISCONNECT THE THERMISTOR CONNECTOR FROM THE PCB (BLACK LEADS)
THERMISTOR
DISCONNECT THE THERMISTOR CONNECTOR FROM THE PCB (BLACK LEADS)
RESISTANCE GAS VALVE AND HARNESS TO EARTH
DISCONNECT THE GAS V
RESISTANCE THERMISTOR TO EARTH
DISCONNECT THE THERMISTOR CONNECTOR FROM THE PCB (BLACK LEADS)
RESISTANCE GAS VALVE AND HARNESS TO EARTH
DISCONNECT THE GAS V
RESISTANCE IGNITION LEAD
DISCONNECT THE IGNITION LEAD ASSEMBLY CONNECTOR FROM THE SPARK ELECTRODE AND FROM THE PCB
OBSERVATION GAS VALVE PASSING
REMOVE BURNER
CONNECT U-GAUGE TO BURNER INJECTOR
FUSE 2A
REMOVE THE FUSE FROM THE PCB
THERMISTOR
DISCONNECT THE THERMISTOR CONNECTOR FROM THE PCB (BLACK LEADS)
AIR PRESSURE SWITCH N/O
REMOVE THE LEADS FROM THE AIR PRESSURE SWITCH (MAKE A NOTE OF THE CONNECTIONS)
FAN HARNESS
DISCONNECT THE BLUE AND PURPLE LEADS FROM THE FAN
DISCONNECT THE 5 PIN PLUG AT THE PCB
PCB FURTHER INVESTIGATION
THE INFORMATION PROV
SPARKING PRESENT
EXTERNAL CONTROLS CALLING FOR HEAT
REMOVE THE COMBUSTION CHAMBER COVER
FAN RUNS AT HIGH SPEED
EXTERNAL CONTROLS CALLING FOR HEAT
FAN RUNS AT HIGH SPEED
EXTERNAL CONTROLS CALLING FOR HEAT
GAS INLET PRESSURE
ATTACH PRESSURE GAUGE TO INLET PRESSURE TEST POINT
EXTERNAL CONTROLS CALLING
IGNITION ELECTRODE AND GAP
DISCONNECT IGNITION LEAD TO THE ELECTRODE
IGNITION LEAD ASSEMBLY
DISCONNECT THE IGNITION LEAD ASSEMBLY CONNECTOR
FROM THE PCB AND ELECTRODE
BURNER PRESSURE
{BLRSTATMAX}
ATTACH PRESSURE GAUGE TO BURNER PRESSURE TEST POINT
RESISTANCE IGNITION LEAD
DISCONNECT THE IGNITION LEAD ASSEMBLY CONNECTOR
FROM THE PCB AND ELECTRODE
GAS VALVE VOLTAGE
EXTERNAL CONTROLS CA
RESISTANCE GAS VALVE AND HARNESS TO EARTH
DISCONNECT THE GAS V
RESISTANCE GAS VALVE AND HARNESS TO EARTH
DISCONNECT THE GAS V
RESISTANCE OVERHEAT THERMOSTAT AND HARNESS
REMOVE THE OVERHEAT CONNECTOR FROM THE PCB
THIS IS THE CONNECTOR WHICH HAS THE 2 BROWN WIRES
OBSERVATION RUN BOILER TO TEMP
{BLRSTATMAX}
ALLOW BOILER TO RUN AND BURNER TO IGNITE.
THERMISTOR
DISCONNECT THE THERMISTOR CONNECTOR FROM THE PCB (BLACK LEADS)
THERMISTOR
DISCONNECT THE THERMISTOR CONNECTOR FROM THE PCB (BLACK LEADS)
RESISTANCE OVERHEAT STAT AT TEMP
{BLRSTATMAX}
System Information
- Total Tests: 217
- Sequence Logic: Decoded from encrypted .seq file
- Navigation: Dynamic based on pass/fail results
- Source: 4731307 GW SWIFTFLOW 100 SIT Control