Set Appliance State:
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Confirm the boilers maximum heating power is set correctly for the CH system the boiler is attached to by entering the diagnostic codes, and reviewing parameter "D.000", this is the maximum KW output for central heating from the appliance.
If the maximum heating output from the appliance is set too low for the size of the installation this will prevent the boiler and system reaching the set temperature.
Click HERE for guidance on how to access and adjust the diagnostic codes.
Alternatively refer to Adapt for guidance.
Note:
Diagnostic code D.000 is set as default to auto
but it can be set between auto - 30KW.
Auto means that the appliance automatically adjusts
the max partial load to the current system demand
If the maximum heating output from the appliance is set too low for the size of the installation this will prevent the boiler and system reaching the set temperature.
Click HERE for guidance on how to access and adjust the diagnostic codes.
Alternatively refer to Adapt for guidance.
Note:
Diagnostic code D.000 is set as default to auto
but it can be set between auto - 30KW.
Auto means that the appliance automatically adjusts
the max partial load to the current system demand