Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
Set Multimeter to DC Volts Set meter to measure DC Volts
Gain access to PCB (use Insulation Mat as required)
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Measurement:

Measure the DC voltage between Pin 14 (Green) on X2
and the earth point on the boiler chassis.
The voltage measured will vary according to the system pressure but should conform approximately to the table below.
System pressureVoltage dc
0 bar1.2
1 bar 1.7
2 bar2.2
3 bar2.8