Set Appliance State:
CH Demand
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Enter the status code display mode on the appliance.
(press and hold the + button for 7 seconds)
The status code and appliance temperature will cycle in the display.
Status codes S07, S53, S54, S96 or S98 indicate an issue with the temperature spread measured by the thermistors.
Is one of the status codes listed above shown?
Note:
To exit status code mode press mode button once.
(press and hold the + button for 7 seconds)
The status code and appliance temperature will cycle in the display.
Status codes S07, S53, S54, S96 or S98 indicate an issue with the temperature spread measured by the thermistors.
Is one of the status codes listed above shown?
Note:
To exit status code mode press mode button once.