Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Attach temperature clamps to flow and return pipes above the appliance as indicated by the red arrows
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Allow the boiler to run with the central heating demand.
(the appliance will not fire but this does not affect the test)
Measure the temperature differential.
Expect a differential of approximately 20°C or less.
Is the temperature differential as expected?
Note.
Initial temperature differential may be greater than 20°C when system is heated from cold.
(the appliance will not fire but this does not affect the test)
Measure the temperature differential.
Expect a differential of approximately 20°C or less.
Is the temperature differential as expected?
Note.
Initial temperature differential may be greater than 20°C when system is heated from cold.