Set Appliance State:
Gas Off
| Isolate Mains Power to appliance as per TOPs P4 |
DHW Demand
Attach pressure gauge to gas valve pressure inlet test point
Gas On
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Reset appliance if required (press reset button for 2 seconds and release).
During the ignition sequence does the inlet pressure remain satisfactory throughout?
Note.
1. It may take approximately 40 seconds for the boiler to recognise
a demand and for the fan to run, this will depend upon the boiler status.
(Status code guidance CLICK HERE)
2. When pressure gauge is removed the pressure test point should be
tightened and checked for gas tightness.
During the ignition sequence does the inlet pressure remain satisfactory throughout?
Note.
1. It may take approximately 40 seconds for the boiler to recognise
a demand and for the fan to run, this will depend upon the boiler status.
(Status code guidance CLICK HERE)
2. When pressure gauge is removed the pressure test point should be
tightened and checked for gas tightness.
Isolate as per TOPs P4
and refit as necessary