Set Appliance State:
CH Demand
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
The fan should run at ignition speed about
20sec after the pump starts.
Check the fan speed by:
Entering the On Board Diagnostics and scroll to d34 using the +/- buttons.
The actual fan speed will be displayed at the top of the screen.
Expect approx. values of 340 LOW rising to 500 HIGH as the fan speed reaches a maximum.
20sec after the pump starts.
Check the fan speed by:
Entering the On Board Diagnostics and scroll to d34 using the +/- buttons.
The actual fan speed will be displayed at the top of the screen.
Expect approx. values of 340 LOW rising to 500 HIGH as the fan speed reaches a maximum.