Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Gain access to pump electrical connections
Observation:
Test 1:
Measure the resistance between the live and neutral connections.
Expect a resistance of approximately 80ohms or greater.
Test 2:
Measure the resistance between the live and earth connections.
Expect a resistance of 1Mohm or greater.
Are the resistances measured as expected?
Note:
Images shown are for illustration purposes only, the pump you have may be different.
Measure the resistance between the live and neutral connections.
Expect a resistance of approximately 80ohms or greater.
Test 2:
Measure the resistance between the live and earth connections.
Expect a resistance of 1Mohm or greater.
Are the resistances measured as expected?