Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
Remove the cover from the pump
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
While the external controls are calling for heat check the voltage at the terminals of the pump.
Expect mains voltage.
NOTE:
The pump is external to the boiler.
If you are unsure as to its location ask the customer for help in finding it.
Expect mains voltage.
NOTE:
The pump is external to the boiler.
If you are unsure as to its location ask the customer for help in finding it.

Isolate as per TOPs P4
and refit as necessary