Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
Disconnect pump speed control at the pump and make safe
Gain access to PCB (use insulation mat as necessary)
Gain access to PCB (use insulation mat as necessary)
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Measurement:
As pump is running during the boiler self check measure the DC voltage
between pin 2 (yellow) and pin 3 (black) at X13 on the PCB.
Voltage should be below 1V DC.
Once pump stops running voltage should change to approximately 4.5V DC.
between pin 2 (yellow) and pin 3 (black) at X13 on the PCB.
Voltage should be below 1V DC.
Once pump stops running voltage should change to approximately 4.5V DC.

Isolate as per TOPs P4
and refit as necessary