Set Appliance State:

Isolate Mains Power to appliance as per TOPs P4
CH Demand
CH temperature control set to MAX
Attach temperature clamps to the flow and return pipes as indicated by the red arrows
WARNING! - Mains voltage is expected during test follow
TOPs P4 live testing procedure
Mains Power On

Observation:

Allow the boiler to run for central heating and the system to heat up.
Measure the temperature differential between the flow and return pipes.
Expect a differential of approx 20°C or less.
Note.
1. Ensure all radiators are open and system is balanced correctly.
2. Initial temperature differential may be greater than 20°C.