Set Appliance State:
| Isolate Mains Power to appliance as per TOPs P4 |
CH Demand
CH temperature control set to MAX
Attach temperature clamps to the flow and return pipes as indicated by the red arrows
Attach temperature clamps to the flow and return pipes as indicated by the red arrows
| WARNING! - Mains voltage is expected during test follow TOPs P4 live testing procedure |
Observation:
Allow the boiler to run for central heating and the system to heat up.
Measure the temperature differential between the flow and return pipes.
Expect a differential of approx 20°C or less.
Note.
1. Ensure all radiators are open and system is balanced correctly.
2. Initial temperature differential may be greater than 20°C.
Measure the temperature differential between the flow and return pipes.
Expect a differential of approx 20°C or less.
Note.
1. Ensure all radiators are open and system is balanced correctly.
2. Initial temperature differential may be greater than 20°C.